Adjustment Parameters - Roland Double Sheet Detector R1000 Series Manual

Inductive principles – microcontroller based
Table of Contents

Advertisement

B0069991 / Rev. 1.7
7.8

Adjustment parameters

Adjustment parameters are parameters, which are only valid for this individual system; they cannot
be transferred to other systems.
Adjustment parameter 1: Zero adjust
The Zero adjust procedure must be performed at commissioning and after having exchanged a
sensor.
Adjust Parameter:
Zero adjust
no
Fig. 67: Status of Zero adjust
Possible choices:
• no:
• all / yes:
During the zero adjust the following message is shown:
Adjust Parameter:
Zero adjust
Zero adjust active
Fig. 68: Display during zero adjust
When the zero adjust is completed, the following message appears:
Adjust Parameter:
Zero adjust
no
Fig. 69: Zero adjust successfully completed
The zero adjust is now completed.
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
Double Sheet Detector-series I20
Before performing a Zero adjust procedure, verify carefully that no
Attention
sheet is in the sensor gap.
1
no Zero adjust to be performed.
All sensors are zero adjusted at the same time.
1
Fault messages are described in the chapter "9 Fault messages".
Note
1
Manual
Maximum time 150 sec.
Start-up
87