Roland Double Sheet Detector R1000 Series Manual page 65

Inductive principles – microcontroller based
Table of Contents

Advertisement

B0069991 / Rev. 1.7
6.3.9
Dynamic Teach-In 1-sheet (Part A)
During the dynamic Teach-In one sheet of nominal thickness must be driven through the sensors.
In the operating mode "Frequency" (Monitoring Parts for Hardend / Tempered Properties and
Materials Mix up) part A must be drive through the sensor gap.
OUT 0
IN 0-9
(without IN 2/3)
IN 3
IN 2
OUT 4, 3, 2, 1 0-1-2-sheet; warning
Check whether the output OUT0 "Enable" has been switched to HIGH (ready for operation), otherwise a
1
fault condition is existing.
Before initiating the Teach-In 1-sheet all inputs must be switched to LOW for 10ms.
2
The Teach-In is selected by switching the input IN3 to HIGH.
3
Switch the input IN2 "Teach-In 1-sheet" to HIGH.
4
Within 10ms the outputs OUT1...OUT4 are switched to LOW.
5
After the sheet has been driven through the sensors the input IN3 is switched to LOW.
6
Now switch the input IN2 "Teach-In 1-sheet" to LOW.
7
The Teach-In is completed within 0,5s and the outputs OUT1...OUT4 switch to HIGH.
8
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
Double Sheet Detector-series I20
Enable
Teach-in
range
Teach-in
1-sheet
1
min.10ms min.10ms
2
3
Manual
max.
10ms
5
Teach-in
range
>= ms
4
6
Communication with the PLC
0,5sec.
7
8
65