18.6.

Display operating times

Properties
Application
Operating time CLOSE
Operating time OPEN
18.7.

Device temperature display

Temp. controls
Temp. control unit
Set maintenance interval
Parameters for setting a defined maintenance interval. Once the set time has elapsed,
a maintenance signal is issued.
Required user level: Specialist (4) or higher.
Operational info collection M1231
Maintenance M1644
Maintenance interval M1233
Default value: 10 years
Setting range: 1 month... 10 years
The integral controls automatically determine the operating time for an operation
between two end positions. For both directions (from OPEN to CLOSE and from
CLOSE to OPEN), the last determined value is saved within a parameter.
Operating time measurement indicates how an actuator installed in plant or a
combination of actuator/gearbox/valve behave with regard to inertia without performing
an operation and measuring the time manually.
Display measured operating times
Operational info collection M1231
Operating time M1232
Operating time CLOSE M1234
Operating time OPEN M1235
Indications:
Indicates the measured operating time for the last operation in direction CLOSE
Indicates the measured operating time for the last operation in direction OPEN
Required user level: Specialist (4) or higher.
Operational info collection M1231
Device temperatures M0524
Indications:
Indication of current temperature in controls housing.
Indication of current temperature in control unit of the actuator (actuator housing).