Operating time: set

SGMR 14.1
Switch steps
SGM/SGMR
04.1
7
55
8
63
9
63
Setting via software parameters (AUMA CDT)
Condition: Switch [S5] is in position ON (software mode).
Setting parameters
Customer settings
Torque switching
Tripping torque CLOSE (S7)
Tripping torque OPEN (S6)
Default value: depending on the order
Setting ranges: adjustable between 40
Operating time is defined by the motor speed.
Setting via switches
Switch [S8] is used to change the motor speed and thus the actuator operating time.
The preset operating time is valid for both operation modes (Local and Remote).
Condition: Switch [S5] is in position OFF (hardware mode).
Figure 24: Switch for operating time
[S8]
Operating time
Default value: depending on the order
Setting range: 9 steps (refer to table)
Table 14:
Switch [S8]
Step
SGM/SGMR
04.1/05.1/07.1
1
63
2
45
3
32
4
22
5
16
6
11
7
Commissioning (basic settings of controls)
Tripping torques [Nm]
SGM/SGMR
SGM/SGMR
SGM/SGMR
05.1
07.1
10.1
110
220
440
125
250
500
125
250
500
100 % of the maximum tripping torque
Operating times for 90° in [s]
SGM/SGMR 10.1
1)
1)
90
1)
1)
63
1)
1)
45
32
22
16
8
11
SGM/SGMR
SGM/SGMR
12.1
14.1
900
2,000
1,000
2,200
1,000
2,200
SGM/SGMR 12.1
SGM/SGMR 14.1
275
206
345
150
103
240
75
175
52
120
41
95
31