Relays Set Up Group

ATTENTION
The Relay set up group parameters are accessible only if relay PWAs are installed in the
actuator. 10260S series actuators can be equipped with up to two relay PWAs –for a total of
four SPDT relays. Using the Relay set up groups you can program the installed relays to
operate in response to various operating conditions.
Table 11lists the parameters and selections available when the SET RELAY n group is selected.
Lower Display
Prompt
RTYPny
n = 1, 2, 3, or 4
y = 1 or 2
RnyE †
RnyVALn = 1,
2, 3, or 4
y = 1 or 2
Rny HLn = 1, 2,
3, or 4
y = 1 or 2
RLYnHY
n = 1, 2, 3, or 4
n is the relay number, y is the relay contact.
Revision 5
10260S HercuLine® Actuator Installation, Operation and Maintenance Manual
7/07
4. Set Up and Calibration Procedures - Relays Set Up Group

Table 11 Relay Set Up Group Parameters

Upper Display
Selections or
Range of Setting
NONE
RELAY TYPE—Selects the relay number and the relay
[default]
activation type. See Table 12 Relay Type Descriptions.
or
Input Range—Upper / lower limits of input signal exceeded
InPR
Position Range—Upper / lower limits of motor position
PosR
Deviation—Deviation from input exceeded
DEV
Upper Limit Travel—Same as PosR for upper limit
ULim
Lower Limit Travel—Same as PosR for lower limit
LLim
Temperature High—High temperature limit exceeded
T Hi
Temperature Low—Low temperature limit exceeded
T Lo
Starts—Motor starts limit exceeded
STRT
Stalled—Motor position does not follow input
STAL
Manual—Actuator is set to manual mode
MAN
Power Up Test Failure—Failure of any power up diagnostic
PWRF
Failsafe Alarm—Failsafe condition detected
FsFA
Position Sensor Signal Failure—NCS output out of valid
PosF
Digital Input—Digital input closure
DiGI
Total Degrees— total degrees traveled.
TDEG
X1
MULTIPLIER—(Relay Type STRTS only) Selects the
or
multiplier for the number limit of motor starts before the relay
X10k
is activated. Multiplier specifies the value on display as
times one (X1) or times ten thousand (X10k).
0.0 to 100.0
RELAY VALUE—Sets numerical value of limit where relay
trips (energizes). Units are determined by the relay type
selection. See Table 12 Relay Type Descriptions for units.
HILO
RELAY HIGH/LOW—Sets relay trip point to high or low limit.
0.0 to 100.0
RELAY HYSTERESIS—0.0 to 100.0% of span or full output.
(in percent)
NOTE: Relay Hysteresis parameter is accessible only if
appropriate relay type is selected.
Parameter Definition
exceeded
† Allows setting of multiplier value.
range
39