Regions of Motor Travel

The full span of motor travel is 90 ° rotation. The span is divided into 10 regions of motor travel as shown
in Figure 24 (regions are numbered 0 through 9). Maintenance statistics are accumulated on the total
number of motor starts, as well as the total number of motor starts that occur in each region of travel. The
statistics can be accessed in the maintenance set up group. The counts can also be reset to zero if desired or
saved manually to memory. See Maintenance Set Up Group for more information. The regions of travel
are set for full span motor travel (90 ° rotation). If the actuator is set up to operate in a smaller range, for
example between 40% and 80% of full span, the maintenance statistics will show motor starts only in
regions 4 through 7.