2. Specifications - Technical and Operating Specifications
Mains Supply
Motor
Motor Current
Fuses
(Motor drive control)
Loss of Power
Local Auto - Manual
Switch
Limit Switches
Auxiliary Switches
Relays
Installation Category
(Overvoltage Category)
Pollution Degree
CE Compliance
CSA/UL
NEMA 4
Clamp Bolt
Rod End Bolt
8
10260S HercuLine® Actuator Installation, Operation and Maintenance Manual
Electrical
120 Vac single phase, 50 or 60 Hz
240 Vac single phase, 50 or 60 Hz
Instant start/stop, non-coasting, non-burnout, continuous duty permanent magnet
synchronous induction motor. Can be stalled up to 100 hours without damage.
= No load = full load = locked rotor
Model No.
10261S, 62S, 64S,
66S
10263S, 10265S
10267S, 68S, 69S
Wickmann USA #373-1160-0-41: 1.6 Amp Fast (2)
Stays in place.
Allows local manual and automatic operation of the actuator. (Optional Feature)
Standard - Two SPDT end of travel limits.
Optional - SPDT switches rated (10 A at 125 Vac, 5 A at 250 Vac).
Optional - Up to 4 SPDT switches rated (5 A at 125 Vac, 2.5 A at 250 Vac).
Category II: Energy-consuming equipment supplied from the fixed installation.
Local level appliances, and industrial control equipment. (EN 61010-1)
Pollution degree 2: Normally non-conductive pollution with occasional conductivity
caused by condensation. (ref. IEC 664-1)
Certifications
Optional
Optional
Optional
Torque Settings of Crank Arm Bolts
Standard Arm (p/n 087449) (1 7/16 to 5 in. adjustment): 85 lb-ft.
Optional Long Arm (p/n 154007) (0-12 in. adjustment): 85 lb-ft.
Standard and long arms: 30-35 lb./ft
120 V, 50/60 Hz
0.4 A (48 VA)
1.0 A (120 VA)
0.8 A (96 VA)
240 V, 50/60 Hz
0.3 A (72 VA)
1.0 A (120 VA)
0.3 A (72 VA)