3. Installation - Before Starting

Before Starting

Unpacking
If there are visible signs of damage to the shipping container, notify the carrier and Honeywell
immediately.
If there is no visible damage, compare the contents with the packing list. Notify the carrier and Honeywell
immediately if there is equipment damage or shortage.
Please do not return goods without contacting Honeywell Applications Center in advance. The contact
number is 1-800-423-9883.

Installation Considerations

Mount the actuator in a location where it will be easily accessible for maintenance and for manual
operation by means of the handwheel. The exact location must be determined in accordance with the
linkage used.
It is important that the actuator be mounted securely to a solid foundation commensurate with the
maximum torque developed. Use studs or bolts that are as large as the foot mounting holes.
The following precautions should be taken when selecting an installation site.
Shield the actuator from rain or snow unless the NEMA 4 option was selected.
Allocate sufficient clearance around the actuator for the removal of all covers to permit inspection of
internal parts and to provide access to the handwheel.
Use auxiliary shielding to protect the actuator from excessive heat or cold outside of the rating of the
Actuator and from corrosive elements
Ambient temperature should not exceed 170 °F (75 °C).
The minimum low temperature limit is –20 °F (–30 °C).

Actuator Mounting

Install the 10260S actuator in a convenient location in any orientation. Firmly bolt the 10260S to a
mounting surface that will not distort when subjected to the torque stresses generated by the actuator. The
output shaft of the actuator should be parallel to the output shaft of the driven device. The output shaft
crank arm is fully adjustable through 360°.

Outline Dimension Drawings

An outline and dimension drawing for actuator mounting is furnished with each unit. Figure 3 and Figure 4
are provided here for reference.