4. Set Up and Calibration Procedures - Calibration
Step
12
Install a new gasket and replace extended cover. Secure to actuator with screws.
13
Continue with calibration procedure in Table 28.
Bottom of NCS spoiler
should be almost horizontal
when properly positioned
Step
1
Reapply AC power to the actuator.
2
Press SET UP key to access the MAINT set up group. Press the FUNCTION key until the
display reads LD CAL.
Press the
3
Perform the Calibrate Motor procedure exactly as in Table 24. Motor calibration must be
performed for full span range.
4
When motor calibration is complete, the calibration is now stored as the factory calibration of
the actuator motor.
66
10260S HercuLine® Actuator Installation, Operation and Maintenance Manual
NCS Spoiler Set Screw
Allen Screw
0.05" Hex
Figure 19 Location of NCS Assembly
Table 28 Load NCS Factory Calibration
or
keys until the display reads POS.
Action
NCS Spoiler
NCS PWA
Action
Revision 5
7/07