Figure 38 Test Relay Function - Honeywell HercuLine 10260S Installation, Operation And Maintenance Manual

Smart actuator
Table of Contents

Advertisement

9. Troubleshooting -
Test Relay Function
Press SET UP
button on keypad
to enter Set up
mode.
Set suspect Relay
type to MAN.
Place ohmmeter
across associated
relay contacts at
Actuator terminal
block. See below.
Relay
RELAY1
RELAY2
RELAY3
RELAY4
104
10260S HercuLine® Actuator Installation, Operation and Maintenance Manual
Set AUTO -
MANUAL switch
to MAN.
Yes
OK

Figure 38 Test Relay Function

Associated Contacts at
Terminal Block
16
NC
17
COM
18
NO
19
NC
20
COM
21
NO
22
NC
23
COM
24
NO
25
NC
26
COM
27
NO
No
Does Relay
operate?
Replace Relay PWA or
Wire harness from Relay
PWA to terminal block.
See Relay replacement
in Maintenance, Section 7.
Revision 5
7/07

Advertisement

Table of Contents
loading

Table of Contents