Table 26 Slidewire Emulation Calibration Procedure - Honeywell HercuLine 10260S Installation, Operation And Maintenance Manual

Smart actuator
Table of Contents

Advertisement

Step
Operation
2,
cont'd
3
Calibrate Span
(100%)
4
Slidewire Emulation
The 10260S Actuator comes already calibrated from the factory. If it becomes necessary to do a calibration
in the field, adjust the output using the procedure in Table 26. Refer to Figure 18 for a diagram to connect a
signal source to the actuator input and a DVM to measure actuator output signal.
ATTENTION
For a slidewire emulation output calibration to be saved, you must complete the procedure.
The calibration will not be saved if you exit without completing the steps of the procedure.
To exit calibration mode, press DISPLAY or SETUP keys.
Step
Operation
1
Enter Calibration
Mode
Revision 5
10260S HercuLine® Actuator Installation, Operation and Maintenance Manual
7/07
Press
Adjust actuator output to a value equal to 0% output as read
or
key
from the DVM.
NOTE: Typically for a 4 mA output, the display will show a value
of approximately 381. A lower limit value is imposed on the zero
output. If the value is 357 or lower, the actuator will not allow you
to calibrate the zero output. The value must be larger than 357
for a valid calibration.
FUNCTION
Upper Display =
Lower Display =
Read meter connected to actuator output.
Adjust actuator output to a value equal to 100% output as read
or
key
from the DVM.
NOTE: Typically for a 20 mA output, the display will show a
value of approximately 1981.
FUNCTION
Calibration for zero and span output values are now stored.
Output calibration is complete.

Table 26 Slidewire Emulation Calibration Procedure

Press
SETUP
Upper Display =
Lower Display =
until you see
FUNCTION
Upper Display =
Lower Display =
Upper Display =
or
key
Lower Display =
4. Set Up and Calibration Procedures - Calibration
Result
xxxx
SPAN
Result
CAL
OUTPUT
DIS
CALOUT
BEGN
CALOUT
63