Set Up and Calibration Procedures

Relays Set Up Group

Relays Set Up Group
ATTENTION
The Relay set up group parameters are accessible only if relay PWAs are installed in the
actuator. HercuLine
relays. Using the Relay set up groups you can program the installed relays to operate in
response to various operating conditions.
Table 13 lists the parameters and selections available when the SET RELAYn group is selected.
Actuator Lower
Display
Prompt
RTYPny
n = 1, 2, 3, or 4
y = 1 or 2
RnyE*
RnyVAL
n = 1, 2, 3, or 4
y = 1 or 2
Rny HL
n = 1, 2, 3, or 4
y = 1 or 2
RLYnHY
n = 1, 2, 3, or 4
n is the relay number, y is the relay contact.
44
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual
®
2001 actuators can be equipped with one PWA –for a total of two SPDT

Table 13 Relay Set Up Group Parameters

Selections or
Range of Setting
RELAY TYPE— Selects the relay number and the relay
NONE
activation type. See Table 14 Relay Type Descriptions.
Input Range— Upper / lower limits of input signal exceeded
InPR
Position Range— Upper / lower limits of motor position
PosR
exceeded
Deviation— Deviation from input exceeded
DEV
Upper Limit Travel— Same as PosR for upper limit
ULim
Lower Limit Travel— Same as PosR for lower limit
LLim
Temperature High— High temperature limit exceeded
T Hi
Temperature Low— Low temperature limit exceeded
T Lo
Starts— Motor starts limit exceeded. Allows setting of
STRT
multiplier value.
Stalled— Motor position does not follow input
STAL
Manual— Actuator is set to manual mode
MAN
Power Up Test Failure— Failure of any power up diagnostic
PWRF
Failsafe Alarm— Failsafe condition detected
FsFA
Position Sensor Signal Failure— position output out of valid
PosF
range
Digital Input— Digital input closure
DiGI
Total Degrees— total degrees traveled. Allows setting of
TDEG
multiplier value.
default = InPR and
NONE
MULTIPLIER— (Relay Types STRT and TDEG only)
X1
Selects the multiplier for the number limit of motor starts and
X10k
total degrees traveled before the relay is activated. Multiplier
default = X1
specifies the value on display as times one (X1) or times ten
thousand (X10k).
RELAY VALUE— Sets numerical value of limit where relay
0.0 to 100.0
trips (energizes). Units are determined by the relay type
selection. See Table 14 Relay Type Descriptions for units.
RELAY HIGH/LOW— Sets relay trip point to high or low
HI
limit.
LO
RELAY HYSTERESIS— 0.0 to 100.0% of span or full output.
0.0 to 100.0
(in percent)
NOTE: Relay Hysteresis parameter is accessible only if
appropriate relay type is selected.
Parameter Definition/PDA HercuLink
®
Prompt
Revision 6
7/07