Communications Set Up Group

Table 14 lists the parameters and selections available for the SET COMM group.
Lower Display
Prompt
COMM
ADDRES
BAUD
XmtDLY
DBLBYT
Revision 5
10260S HercuLine® Actuator Installation, Operation and Maintenance Manual
7/07
4. Set Up and Calibration Procedures - Communications Set Up Group

Table 14 Communications Set Up Group Parameters

Upper Display
Selections or
Range of Setting
COMMUNICATONS PARAMETERS—Disables or enables
parameter displays for Modbus communciations set up.
DIS
Disabled—Locks out access to communications displays
and parameters.
MODB
Modbus—Allows access to the communication displays and
settings for the parameters listed below.
HART
HART - Selects HART as the Communications Protocol.
1 to 99
DEVICE ADDRESS—Selects device address when used in
a Modbus communications loop. Select an address that is
unique to other devices on the communications link.
2400
BAUD RATE—Selects the speed of data transfer. All
4800
equipment on the link must be set to match the host setting.
9600
19.2k
NONE
RESPONSE DELAY—Selects the time delay (in
10ms
milliseconds) before a response to a query is transmitted.
20ms
30ms
40ms
50ms
FLOATING POINT DATA FORMAT—Selects the format for
transferring floating point data.
FP B
Floating Point Big Endian format—
FPBB
Floating Point Big Endian format
FP L
Floating Point Little Endian format—
FPLB
Floating Point Little Endian format
Parameter Definition
with byte-swapped—
with byte-swapped—
Byte Order
0 1 2 3
1 0 3 2
3 2 1 0
2 3 0 1
45