Signal Contact - Festo MS6-SV-E Operating Instructions Manual

Soft-start/quick exhaust valve
Table of Contents

Advertisement

Available languages

Available languages

MS6-SV-...-E-10V24
4.4

Signal contact

The signal contact is a potential-free N/O contact of a semiconductor relay. Through terminals 3 and 4
of the NECA-... multi-pin plug socket, the contact can be picked up in the feedback circuit of a safety
control system.
Note
Operation of the signal contact outside the permitted technical data results in its irre-
parable failure. Compliance with the specification must be ensured through an appro-
priate protective circuit.
Note
Assignment of these contacts is not required to achieve the safety category.
Fig. 10
Feedback signal connection
The diagrams for the switching characteristics can be found in the chapter 14 "Technical data" (with
multi-pin plug socket NECA-S1G9-P9-MP1
S1G9-P9-MP3/MP5
Status of valve
Activation for pressurisation through EN1 and EN2
Activation for exhaust through EN1 and EN2
Malfunction (red LED flashing)
Supply voltage is not connected
Tab. 3
Switching statuses of the signal contact
Festo – MS6-SV-...-E-10V24 – 1310b English
Fig. 20; with multi-pin plug socket NECA-
Fig. 22).
Signal contact
Open
Closed
Open
Open