AUMA AC 01.2 Manual page 134

Actuator controls
Hide thumbs Also See for AC 01.2:
Table of Contents

Advertisement

Appendix
Signal
Actuator running
Running LOCAL
Running REMOTE
Handwheel oper.
In intermediate pos.
Intermediate pos. 1
Intermediate pos. 2
Intermediate pos. 3
Intermediate pos. 4
Intermediate pos. 5
Intermediate pos. 6
Intermediate pos. 7
Intermediate pos. 8
Input DIN 1
Input DIN 2
Input DIN 3
Input DIN 4
Input DIN 5
Input DIN 6
EMCY stop active
Torque fault CLOSE
Torque fault OPEN
Torque fault
Thermal fault
Phase fault
Handwheel active
PVST active
PVST fault
PVST abort
Failure (configurable)
Interlock Remote
Interlock Local
Interlock OPEN
Interlock CLOSE
Interlock
Bypass Sync Out
Interlock by-pass
Safe ESD
Safe Stop
SIL fault
SIL function active
System ok
134
Description
Actuator is running (output drive is moving)
Hard wired collective signal consisting of:
Running LOCAL
Running REMOTE
Handwheel oper.
Output drive rotates due to operation command from LOCAL.
Output drive rotates due to operation command from REMOTE.
Output drive rotates without electric operation command.
The actuator is in an intermediate position e.g. neither in end position OPEN nor in end pos-
ition CLOSED.
Intermediate position 1 reached
Intermediate position 2 reached
Intermediate position 3 reached
Intermediate position 4 reached
Intermediate position 5 reached
Intermediate position 6 reached
Intermediate position 7 reached
Intermediate position 8 reached
A high signal (+24 V DC) is present at digital input 1.
A high signal (+24 V DC) is present at digital input 2.
A high signal (+24 V DC) is present at digital input 3.
A high signal (+24 V DC) is present at digital input 4.
A high signal (+24 V DC) is present at digital input 5.
A high signal (+24 V DC) is present at digital input 6.
Operation mode EMERGENCY stop is active (EMERGENCY stop button has been pressed).
Torque fault in direction CLOSE
Torque fault in direction OPEN
Torque fault in directions CLOSE or OPEN
Motor protection tripped
One phase missing
Manual operation is active (handwheel is engaged); optional signal.
Partial Valve Stroke Test (PVST) is active.
Partial Valve Stroke Test (PVST) could not be successfully completed.
Partial Valve Stroke Test (PVST) was aborted or could not be started. Remedy: Perform
RESET or restart PVST.
This signal can be configured (parameter Failure (configurable) M0879) and comprises a
combination of the following signals which can also be configured:
Fault (Cfg) M0880
Warnings (Cfg) M0881
Not ready REMOTE (Cfg) M0882
Function Interlock is active for operation mode REMOTE.
Function Interlock is active for operation mode Local.
Interlock OPEN is active (enable signal for operation commands in direction OPEN available).
Interlock CLOSED is active (enable signal for operation commands in direction CLOSE
available).
The operation mode Interlock is active.
<By-pass function> enable for operation commands of main or by-pass valves is active.
Operation command executed without enable signal Bypass Sync Out.
Safe ESD function (Emergency Shut Down) is active.
Safe STOP function is active.
A SIL fault has occurred (collective signal).
A SIL function is active. Collective signal of both states, Safe ESD or Safe STOP.
The actuator is switched on and no fault is present
Actuator controls
AC 01.2/ACExC 01.2