Application functions

8.
Application functions
Definition
8.1.

Intermediate positions (pivot points)

Conditions
Characteristics
8.1.1.

Intermediate positions (pivot points): define

Information
8.1.2.

Signal behaviour of intermediate positions: set

No signal
C________|¯¯¯¯¯¯¯¯O
C¯¯¯¯¯¯¯¯¯|_______O
C_______|¯|_______O
46
Application functions are functions used to adapt the AC to special applications. This
includes device functions, communication functions and device information.
If they are enabled, these functions can be programmed by the user for his/her
specific task using parameters.
Option
The actuator is equipped with a position transmitter.
With the AC, up to 8 intermediate positions (pivot points) can be set to any
value between 0 % and 100 % of the travel.
Each intermediate position can be activated or deactivated individually.
When reaching an intermediate position, a signal can be generated.
A hysteresis can be defined for each pivot point.
Each intermediate position can be set to a value between 0 and 100 % of the travel.
Customer settings M0041
Intermediate positions M0143
Pivot points M0160
Pivot point 1 M0249
Default values: 0.0 % for all 8 intermediate positions
Setting range: 0.0 % (CLOSED) to 100.0 % (OPEN) of the travel
The pivot points also apply to the <Operation profile> function.
Reaching a pivot point (intermediate position) can be signalled:
via indication lights (LEDs) of the local controls or
via output contacts
Each pivot point (intermediate position) can be assigned a specific signal behaviour.
Customer settings M041
Intermediate positions M0143
Signal behaviour M0266
Signal behaviour 1 M0269
Default value: No signal
Setting values:
Behaviour A: "Off", intermediate position is not signalled.
Behaviour B: Signal is active from reaching the pivot point (P) up to end position
OPEN (100 %)
Behaviour C: Signal is active from end position CLOSED (0 %) until reaching the
pivot point (P).
Behaviour D: When passing the pivot point (P), a pulse signal is issued.