AUMA AC 01.2 Manual page 34

Actuator controls
Hide thumbs Also See for AC 01.2:
Table of Contents

Advertisement

Operation
Off (push-to-run op.)
OPEN
CLOSE
OPEN and CLOSE
OPEN & CL w/o STOP
Off
CCW
CW
CW and CCW
CW & CCW w/o STOP
34
Self-retaining = Off (push-to-run op.)
Self-retaining Remote II = OPEN and CLOSE
Setting values for parameters, Self-retaining Remote M0100 and Self-retaining
Remote II M0101:
Push-to-run operation activated, self-retaining off:
Actuator only runs in directions OPEN or CLOSE while an operation command is
being received. The actuator stops if the operation command is cancelled.
In direction OPEN = self-retaining (in direction CLOSE push-to-run operation):
After an operation command in direction OPEN, the actuator continues to run, even
if the operation command is cancelled (self-retaining). The actuator is either stopped
by the STOP command or if end position OPEN or an intermediate position OPEN
has been reached.
In direction CLOSE = self-retaining (in direction OPEN push-to-run operation):
After an operation command in direction CLOSE, the actuator continues to run, even
if the operation command is cancelled (self-retaining). The actuator is either stopped
by the STOP command or if end position CLOSED or an intermediate position
CLOSED has been reached.
In directions OPEN and CLOSE = self-retaining:
After an operation command, the actuator continues to run in directions OPEN or
CLOSE, even if the operation command is cancelled (self-retaining). The actuator
is either stopped by the STOP command or if an end position or intermediate position
has been reached.
Direct reversal of operation is not possible. Operation commands in directions OPEN
or CLOSE must be stopped first by the STOP command.. Only then is an operation
command into the opposite direction allowed.
In directions OPEN and CLOSE = self-retaining without stop:
Direct reversal of the operation direction without STOP command is possible.
Direct reversal of operation is also possible without the STOP command. However,
operation can be stopped at any time by the STOP command.
Setting values for parameter Self-retaining M01193 (for Multiport Valve function):
Push-to-run operation activated, self-retaining off:
The actuator will only be operated clockwise or counterclockwise as long as an
operation command (CW or CCW) is present. The actuator stops if the operation
command is cancelled.
Counterclockwise (CCW) = self-retaining (clockwise = push-to-run operation):
After an operation command in CCW direction, the actuator continues to run, even
if the operation command is cancelled (self-retaining). The actuator is either stopped
by the STOP command or if the specified MPV position has been reached.
Clockwise (CW) = self-retaining (counterclockwise = push-to-run operation):
After an operation command in CW direction, the actuator continues to run, even if
the operation command is cancelled (self-retaining). The actuator is either stopped
by the STOP command or if the specified MPV position has been reached.
In both directions = self-retaining:
After an operation command (in CW or CCW direction), the actuator continues to
run, even if the operation command is cancelled (self-retaining). The actuator is
either stopped by the STOP command or if an MPV position has been reached.
Direct reversal of operation is not possible. Operation commands in CW or CCW
directions must be stopped first by the STOP command.. Only then is an operation
command into the opposite direction allowed.
In both directions = self-retaining without stop:
Direct reversal of the operation direction without STOP command is possible.
Actuator controls
AC 01.2/ACExC 01.2