Maintenance (Information And Signals) - AUMA AC 01.2 Manual

Actuator controls
Hide thumbs Also See for AC 01.2:
Table of Contents

Advertisement

Plant Asset Management
14.5.

Maintenance (information and signals)

Characteristics
Application
Function not active
Function active
Function not active
Function active
122
Starting date:.
Saving date:.
Scaling:.
AC actuator controls monitor various parameters set in the factory which have an
impact on the wear of the actuator. Once one of these parameters exceeds a
determined limit, actuator controls generate a signal:
Status indication: S0005 Warnings (AUMA category)
-
Details: Maintenance required
Status indication: S0010 Maintenance required (NAMUR category)
-
Details: shows the parameter(s) for which the limit was exceeded, causing
the Maintenance required signal.
Apart from the parameter monitoring preset in the factory (MT lifetime
mechanics/O-rings/lubricant/contactors), a fixed maintenance interval can additionally
be configured, triggering the same signal when exceeding the configured time.
The current maintenance status of the monitored parameters is represented in a bar
chart.
Once maintenance is complete, the parameter initiating maintenance must be reset
to zero.
Maintenance on demand, i.e. the function can be used to perform maintenance
depending on the intensity and load of the actuator.
Activate maintenance signals
Required user level: Specialist (4) or higher.
Device configuration M0053
Application functions M0178
Activation M0212
Maintenance signals M1136
Default value: Function not active
Setting values:
<Maintenance signals> function deactivated.
<Maintenance signals> function activated.
Activate <Maintenance interval> function
Required user level: Specialist (4) or higher.
Device configuration M0053
Application functions M0178
Activation M0212
Maintenance interval M1137
Default value: Function not active
Setting values:
<Maintenance interval> function deactivated.
<Maintenance interval> function activated.
Display maintenance information
Maintenance signals M1231
Maintenance M1644
Maintenance informat. M1037