Application functions
8.9.8.

Operate to position from Remote

Example
8.9.9.

Dead band

8.9.10.

Backlash compensation

72
Symbol
Set positions (of valve ports)
P
(P1, P2, ...) selected position (1, 2, ...)
– – / –N/A–
No position has been selected.
E2
Actual position value
To interrupt an operation (triggered operation command):
→ Select "– – / –N/A–" during operation, and confirm via Ok (push button
actuator stops in its current position.
For direct operation to position from remote, make sure that selector switch position
Remote control (REMOTE) is selected.
Operation to position via digital inputs
An input (DIN) must be configured for each position (valve port).
Configuration of digital inputs
Required user level: Specialist (4) or higher.
Device configuration M0053
I/O interface M0139
Digital inputs M0116
DIN4 input to operate to position 1 selecting the shortest path:
Parameter: Signal DIN 4 M0118 = Intermediate pos. 1
Setting values for digital inputs (DIN)
Intermediate pos. 1 to
Intermediate pos. 12
MPV: CW Position 1 to
MPV: CW Position 10
MPV: CCW Position 1 to
MPV: CCW Position 10
MPV DriveCW
MPV DriveCCW
The dead band prevents operation to a new setpoint position within a specified band.
Required user level: Specialist (4) or higher.
Customer settings M0041
Multiport valve M1140
Reduction ratio M1143
Default value: 0.00°
Setting range: 0.00 – 36.0° (degrees)
Adjustable backlash compensation of the overall system including valve coupling.
Required user level: Specialist (4) or higher.
Customer settings M0041
Multiport valve M1140
Backlash comp. M1146
Default value: 0.00°
Operation behaviour for input control
Operation to defined position while selecting the
shortest path
Operation to defined position in clockwise direction
Operation to defined position in counterclockwise
direction
Actuator operation in clockwise direction (without
stop at any position)
Actuator operation in counterclockwise direction
(without stop at any position)
Actuator controls
AC 01.2/ACExC 01.2
). The