Lpv Function: Activate; Lpv Actuator Type: Configure; Delay Time Of Master Lpv Actuator: Configure - AUMA AC 01.2 Manual

Actuator controls
Hide thumbs Also See for AC 01.2:
Table of Contents

Advertisement

Actuator controls
AC 01.2/ACExC 01.2
8.8.1.

LPV function: activate

Function not active
Function active
8.8.2.

LPV actuator type: configure

MA master actu./rotat.
SA slave act./stroke
8.8.3.

Delay time of master LPV actuator: configure

Required user level: Specialist (4) or higher.
Device configuration M0053
Application functions M0178
Activation M0212
LPV function M1087
Default value: Function not active
Setting values:
Function deactivated.
Function activated.
Required user level: Specialist (4) or higher.
When using the LPV function, it must be defined for each actuator controls whether
it controls the master or the slave actuator.
Customer settings M0041
Lift Plug Valve M1089
LPV application M1090
Default value: MA master actu./rotat.
Setting values:
Actuator controls/actuator act as master actuator is in charge of the rotation of the
closing element.
Actuator controls/actuator act as slave actuator is in charge of the stroke of the
closing element.
Configure delay time for operation in direction OPEN
A delay time for operation in direction OPEN can be defined in end position CLOSED
of the master actuator. When reaching end position OPEN of the slave actuator, the
procedure for opening valve will be delayed by this time. The master actuator will
then run in direction OPEN.
Required user level: Specialist (4) or higher.
Customer settings M0041
Lift Plug Valve M1089
Delay MA direct.OPEN M1091
Default value: 02:00.0
Setting ranges: 00:00,0 ... 15:00.0 min:s (minutes:seconds)
Configure delay time for operation in direction CLOSE
A delay time for operation in direction CLOSE can be defined in end position OPEN
of the master actuator. When reaching end position OPEN of the slave actuator, the
procedure for closing valve will be delayed by this time. The master actuator will then
run in direction CLOSE.
Required user level: Specialist (4) or higher.
Customer settings M0041
Lift Plug Valve M1089
Delay MA direct.CLOSE M1092
Default value: 00:00.0
Setting ranges: 00:00.0 15:00.0 min:s (minutes:seconds)
Application functions
67