The <Asset Management> function provides information (operational data, signals,
reports and characteristics), which can be used within an Asset Management System
but also generally for support during commissioning, maintenance or corrective
action.
Operating data provides details e.g. about the running time, the number of starts,
number of torque faults etc.
The analysis of this data provides valuable information regarding the optimization of
both actuator and valve. When using this information purposefully, actuator and valve
will be carefully operated, e.g. through appropriate parameter setting. In case of
faults, the logging of operating data allows for quick fault diagnostic.
View the operating data
Two counters are available, a lifetime counter and a resettable counter.
Asset Management M1231
Operational info M0177
Operational info total M0183
Operational info M0188
Description of the indications:
Operational info total = Lifetime counter
Operational info = Counter can be reset to 0
Table 14: Operating data
Indication on display
Motor running time
Motor starts
No. thermal faults
Torque fault CLOSE
Torque fault OPEN
Limit trip CLOSED
Limit trip OPEN
Torque trip CLOSE
Torque trip OPEN
On time warning 1
On time warning 2
No. system starts
Max. tem. controls
Min. temp. controls
Max. temp. MWG
Min. temp. MWG
Max. vibration
Operating hours
Reset operating data
Required user level: Specialist (4) or higher.
Asset Management M1231
Operational info M0177
Reset operation. info M0197
Description
Motor running time
Number of motor starts (starts)
Number of thermal faults (motor protection)
Number of torque faults in direction CLOSE
Number of torque faults in direction OPEN
Number of limit switch trippings in direction CLOSE
Number of limit switch trippings in direction OPEN
Number of torque switch trippings in direction CLOSE
Number of torque switch trippings in direction OPEN
Total of all time intervals during which a start/run warn-
ing was signalled.
Max. time interval during which a start/run warning was
signalled.
Total of AUMATIC system starts
Maximum temperature of the controls
Minimum temperature of the controls
Maximum temperature of the MWG
Minimum temperature of the MWG
Maximum vibration of actuator
Operating hours counter: Number of hours during which
controls are supplied with power