Failure functions
OPEN
CLOSE
OPEN and CLOSE
9.7.

Local Stop

Characteristics
Information
9.7.1.

Behaviour

Off
Sel.sw.Local + Remote
Information
9.8.

EMERGENCY stop function

Conditions
Characteristics
88
Customer settings M0041
Interlock M0664
Running dir. Interlock M0666
Default value: OPEN and CLOSE
Setting values:
The enable signal is only required for operation commands in direction OPEN.
The enable signal is only required for operation commands in direction CLOSE.
The enable signal is required for operation commands in directions OPEN and
CLOSE.
Option
The function Local Stop can be used to stop an operation from Remote locally
with the push button STOP.
All operation commands are interrupted.
After releasing push button STOP, and operation command which might still be
present will become active immediately.
Required user level: Specialist (4) or higher.
Customer settings M0041
Local controls M0075
Local STOP M0627
Default value: Off
Setting values:
Push button STOP can only interrupt an operation in operation mode Local (selector
switch = position Local control).
In the operation modes Local, Remote, Remote II, EMERGENCY and Service, push
button STOP interrupts an operation.
In operation mode Disabled, an interruption is NOT possible.
Option
An EMERGENCY stop button (latching) is either located on the electrical connection
or outside.
In an emergency, the EMERGENCY stop button can be used to interrupt the
power supply of the motor control (contactors or thyristors). Possibly present
operation commands with self-retaining will be reset
The indication in the top row of the display shows: EMCY stop