Operation Profile (Operation Behaviour) For Intermediate Positions; Operation Profile: Activate; Operation Behaviour For Intermediate Positions (Pivot Points): Set - AUMA AC 01.2 Manual

Actuator controls
Hide thumbs Also See for AC 01.2:
Table of Contents

Advertisement

Application functions
Information
8.2.

Operation profile (operation behaviour) for intermediate positions

Conditions
Characteristics
8.2.1.

Operation profile: activate

Function not active
Function active
8.2.2.

Operation behaviour for intermediate positions (pivot points): set

Off
Stop in OPEN
Stop in CLOSED
Stop in OPEN & CL.
Off time in OPEN
48
Hysteresis M0267
Hysteresis 1 M0277
Default values: 0.5 % for all 8 positions
Setting range: 0.0 % to 5.0 % of the travel (from OPEN to CLOSED)
For signal behaviour D, the value XT (Outer dead band M0148 parameter) determines
pulse duration pT and influences switch-on point P1.
Option
Function <Positioner>, parameter Positioner M0158 = Function active (Required
user level: Specialist (4) or higher)
The function <Operation profile> can be used to define the operation behaviour of
the actuator when reaching an end position. Example: The actuator stops and only
continues its operation after another operation command.
This function is required in special applications to avoid water hammer, possibly also
in combination with the timer.
Required user level: Specialist (4) or higher.
Device configuration M0053
Application functions M0178
Activation M0212
Operation profile M0294
Default value: Function not active
Setting values:
Function <Operation profile> deactivated.
Function <Operation profile> activated.
When reaching an intermediate position, the operation behaviour of the actuator
may be set.
Customer settings M0041
Intermediate positions M0143
Operation behaviour M0257
Operation behaviour 1 M0258
Default value: Off
Setting values:
No intermediate stop, actuator continues the operation.
Actuator stops at pivot point during operation in direction OPEN.
Another operation command must be issued to resume operation.
This function is not active in the operation mode Remote SETPOINT.
Actuator stops at pivot point during operation in direction CLOSE.
Another operation command must be issued to resume operation.
This function is not active in the operation mode Remote SETPOINT.
Actuator stops automatically upon reaching the pivot point.
Another operation command must be issued to resume operation.
This function is not active in the operation mode Remote SETPOINT.
Actuator stops at pivot point during operation in direction OPEN. If an operation
command in direction OPEN is present at the end of the pause time, the actuator