Diagnostic Process Controller; Diagnostic Fqm (Fail Safe); Simulation (Inspection And Test Function); 13.11.1. Actuator Signals - AUMA AC 01.2 Manual

Actuator controls
Hide thumbs Also See for AC 01.2:
Table of Contents

Advertisement

Diagnostics
13.9.

Diagnostic Process controller

13.10.

Diagnostic FQM (fail safe)

13.11.

Simulation (inspection and test function)

13.11.1. Actuator signals

112
Parameters
On time/h
Starts/h
Required user level: Specialist (4) or higher.
Diagnostic M0022
Process controller M0883
Menu M0883 is only visible if function Process controller M0741 is activated.
The following states can be checked via diagnostic:
Parameters
Process setpoint
Actual process value
Op. com. PID contr.
The menu will only be visible if a fail safe unit (FQM) is connected to the actuator.
Required user level: Observer (1) or higher.
Diagnostic M0022
FO cables M0638
The following states can be checked via diagnostic:
Parameters
FQM FS ready
FQM FS diag. result
FQM fail safe end.pos.
FQM FS-PosOk
FQM request
FQM timeout tension
The service personnel or the commissioning engineer can use this simulation function
to simulate the operation and failure behaviour of the actuator or the AUMATIC to
check the interface to the DCS and the correct behaviour of the DCS.
By simulating the actuator signals, the signal behaviour of the AUMATIC to the DCS
can be tested, for example, without having to connect the actuator.
Required user level: Service (5) or higher.
Diagnostic M0022
Simulation M0023
Actuator signals M0024
Menu ID
Signification
M0594
Current on time/h
M0595
Current starts/h
Menu ID
Signification
M0884
Process setpoint of PID controller
M0885
Actual process value of PID controller
M0886
Calculated setpoint position for subordinate controller
Menu ID
Signification
M1725
"FQM FS ready" active means that the FQM unit is
ready to perform a fail safe operation
M1726
"FQM FS diag. result" active means that the diagnostic
result of winding and blinker contact is indicated as
faulty.
M1727
FQM (fail safe) is in end position corresponding to the
fail safe position (depending on the configuration, this
can be OPEN or CLOSED)
M1728
- "FQM FS-PosOk" active means, that constant force
spring and toggle lever switch are both operation (the
solenoid switch is being controlled).
M1729
Fail safe function of FQM (fail safe) is requested. (ESD
requested).
M1730
"FQM timeout tension" active means, that the winding
procedure was not completed within the permissible
initialisation time of 2.5 minutes.
Actuator controls
AC 01.2/ACExC 01.2

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Acexc 01.2