Corrective action
Table 16: Warnings and Out of specification
Indication on display
Config. warning
Internal warning
24 V DC external
Wrn on time running
Wrn on time starts
Failure behav. active
Wrn input AIN 1
Wrn input AIN 2
Wrn setpoint position
Op. time warning
Wrn controls temp.
Wrn motor temp.
Wrn gearbox temp.
Time not set
RTC voltage
PVST fault
PVST abort
Wrnn no reaction
Wrn FOC
Wrn FO cable budget
126
Description/cause
Collective signal 06:
Possible cause:
Configuration setting is incorrect.
The device can still be operated with restric-
tions.
Collective signal 15:
Device warnings
The device can still be operated with restric-
tions.
The external 24 V DC voltage supply of the
controls has exceeded the power supply limits.
Warning on time max. running time/h ex-
ceeded
Warning on time max. number of motor starts
(starts) exceeded
The failure behaviour is active since all re-
quired setpoints and actual values are incor-
rect.
Warning: Loss of signal analogue input 1
Warning: Loss of signal analogue input 2
Warning: Loss of signal of actuator setpoint
position
Possible causes:
Input signal for setpoint = 0 (signal loss)
The set time (parameter Perm.op. time,
manual M0570) has been exceeded. The
preset operating time is exceeded for a com-
plete travel from end position OPEN to end
position CLOSED.
Temperature within controls housing too high
Temperature within motor winding too high
Temperature within actuator gear housing too
high
Real time clock has not yet been set.
Voltage of the RTC button cell is too low.
Partial Valve Stroke Test (PVST) could not be
successfully completed.
Partial Valve Stroke Test (PVST) was aborted
or could not be started.
No actuator reaction to operation commands
within the set reaction time.
Optical receiving signal (channel 1) incorrect
(no or insufficient Rx receive level) or RS-485
format error (incorrect bit(s))
Warning: FO cable system reserve reached
(critical or permissible Rx receive level)
Actuator controls
AC 01.2/ACExC 01.2
Remedy
Details to display a list
Press push button
of individual indications.
For a description of the individual signals refer
to <Individual signals> table/ Config. warning
(collective signal 06).
Details to display a list
Press push button
of individual indications.
For a description of the individual signals refer
to <Individual signals> table/ Internal warning
(collective signal 15).
Check 24 V DC voltage supply.
Check modulating behaviour of actuator.
Check parameter Perm. running time/h
M0356, re-set if required.
Check modulating behaviour of actuator.
Check parameter Permissible starts/h
M0357, re-set if required.
Verify signals:
Setpoint E1
Actual value E2
Actual process value E4
Check wiring.
Check wiring.
Check setpoint signal.
The warning indications are automatically
cleared once a new operation command is
executed.
Check valve.
Check parameter Perm.op. time, manual
M0570.
Measure/reduce ambient temperature.
Check actuator sizing, correct accordingly.
Check actuator sizing, correct accordingly.
Set time.
Replace button cell.
Check actuator (PVST settings).
Perform RESET or restart PVST.
Check movement at actuator.
Check parameter Reaction time M0634.
Check/repair FO cables.
Check/repair FO cables.