8.9.11.

Signalling behaviour of positions: set/check

No signal
C________|¯¯¯¯¯¯¯¯O
C¯¯¯¯¯¯¯¯¯|_______O
C_______|¯|_______O
Information
8.9.12.

Hysteresis for signalling intermediate positions: set

Example
Setting range: 0.00 – 36.0° (degrees)
Reaching of a point (valve port) can be signalled:
via indication lights (LEDs) of the local controls or
(refer to chapters <Indications> <Indication lights>)
via output contacts
(refer to chapters <Indications> <Assignment of outputs>)
Signal behaviour, this means the signal behaviour upon reaching a position, is set
via parameter Signal behaviour.
Customer settings M0041
Multiport valve M1140
Signal behaviour M1147
Default value: No signal
Setting values:
A: Signal behaviour Off. Position is not signalled.
B: Signal is active from reaching the position up to 360°.
C: Signal is active from 0° until the position is reached.
D: When passing the position, a pulse signal is issued. The pulse range (range +/–
around the pivot point) depends on the set hysteresis.
Figure 52: Signal behaviour of positions
The set signal behaviour is valid for all positions.
The hysteresis determines the tripping point.
Parameter Position 4 M1153 is set to 180° (50 % of the travel).
Parameter Hysteresis M1148 is set to 3.0°.
Application functions
73