Short instructions
3.4
Remote position transmitter
3.5
AUMA MATIC on wall bracket
Figure B-5: AM on wall bracket
Connection cable to actuator
3.6
Test run
For the connection of remote position transmitters (potentiometer, RWG)
screened cables must be used.
The AUMA MATIC can also be mounted separately from the actuator on a
.
wall bracket.
For the connection of actuator and AUMA MATIC on wall bracket, use suit-
able flexible and screened connecting cables.
.
(Preconfectioned cables can be obtained from AUMA on request)
Permissible cable distance between actuator and AUMA MATIC amounts
.
to a max. of 100 m.
Versions with potentiometer in the actuator are not suitable. Instead of the
.
potentiometer, an RWG has to be used in the actuator.
Connect the wires in correct phase sequence.
Check direction of rotation before switching on.
The plug connection on the wall bracket is made as crimp version.
Use a suitable four indent crimp tool for crimping.
Cross sections for flexible wires:
Control cables:
max. 0.75 to 1.5 mm²
Power supply:
max. 2.5 to 4 mm²
The connector at the actuator is equipped with screw type connections.
Wire end sleeves have to be used.
Perform test run. Please refer to the operation instructions pertaining to the
actuator (multi-turn actuator SA(R) .../part-turn actuator SG ...).
Check limit and torque switching:
Check limit and torque switching, electronic position transmitter RWG or
potentiometer (option) and re-set where appropriate.
The settings are described in the operation instructions pertaining to the
actuator (multi-turn actuator SA(R) ... part-turn actuator SG ... ).
For actuators with feedback signal (RWG, potentiometer), a reference
operation has to be performed after having changed the setting.
.
Perform reference operation:
Operate actuator electrically (via the push buttons OPEN and CLOSE of
the local controls) once to the end position OPEN and once to the end
.
position CLOSED.
If no reference operation is performed after changing the limit switching,
the feedback signal via the bus is not correct. The bus signals the missing
reference operation as warning.
Actuator controls AUMA MATIC AM/AMExB/AMExC
Modbus
7