Application Functions; Intermediate Positions; Intermediate Positions Of Pivot Points: Define; Signal Behaviour Of Intermediate Positions: Set - AUMA AC 01.2 Manual

Actuator controls
Hide thumbs Also See for AC 01.2:
Table of Contents

Advertisement

Actuator controls
AC 01.2/ACExC 01.2 Profinet
8.

Application functions

Definition
8.1.

Intermediate positions

Conditions
Characteristics
8.1.1.

Intermediate positions of pivot points: define

Information
8.1.2.

Signal behaviour of intermediate positions: set

No signal
C________|¯¯¯¯¯¯¯¯O
C¯¯¯¯¯¯¯¯¯|_______O
C_______|¯|_______O
Application functions are functions used to adapt the actuator controls to special
applications. This includes device functions, communication functions and device
information.
If they are enabled, these functions can be programmed by the user for his/her
specific task using parameters.
The actuator is equipped with a position transmitter.
With the actuator controls, up to 8 intermediate positions can be set to any
value between 0 % and 100 % of the travel.
Each intermediate position can be activated or deactivated individually.
When reaching an intermediate position, a signal can be generated.
A hysteresis can be defined for each pivot point.
Each intermediate position can be set to a value between 0 and 100 % of the travel.
Customer settings M0041
Intermediate positions M0143
Pivot points M0160
Pivot point 1 M0249
Default values: 0.0 % for all 8 intermediate positions
Setting range: 0.0 % (CLOSED) to 100.0 % (OPEN) of the travel
The pivot points also apply to the <Operation profile> function.
Reaching a pivot point (intermediate position) can be signalled:
via fieldbus (refer to separate operation instructions)
via indication lights (LEDs) of the local controls or
via output contacts
Each pivot point (intermediate position) can be assigned a specific signal behaviour.
Customer settings M0041
Intermediate positions M0143
Signal behaviour M0266
Signal behaviour 1 M0269
Default value: No signal
Setting values:
Behaviour A: "Off", intermediate position is not signalled.
Behaviour B: Signal is active from reaching the pivot point (P) up to end position
OPEN (100 %)
Behaviour C: Signal is active from end position CLOSED (0 %) until reaching the
pivot point (P).
Behaviour D: When passing the pivot point (P), a pulse signal is issued.
Application functions
47

Advertisement

Table of Contents
loading

This manual is also suitable for:

Acexc 01.2

Table of Contents