Module-Related Rules For Configuration; Connecting The Cables And Plugs To The Manifold Block - Festo CPX-FVDA-P2 Original Instructions Manual

Output module
Hide thumbs Also See for CPX-FVDA-P2:
Table of Contents

Advertisement

Installation
3.1.1

Module-related rules for configuration

Only plug the output module CPX-FVDA-P2 into the interlinking block CPX-M-GE-EV-FVO or the
pneumatic interface VABA-S6-1-X...-F1/F2-CB.
A mechanical coding prevents the output module from being plugged into an incorrect interlinking
block.
Note that the manifold blocks and the pneumatic interface are not mechanically coded.
Only operate the output module with manifold blocks CPX-M-AB-4-M12X2-5POL or
CPX-AB-8-KL-4POL or the pneumatic interface VABA-S6-1-X...-F1/F2-CB.
When placing the output module, ensure that the voltage 24 V
it through output channel CH0 and that the voltage 24 V
Use the output module only in combination with permissible product versions of the CPX terminal
or the valve terminal VTSA-F-CB è 2.1.3 Supported product versions.
NOTICE!
The power supply U
OUT
If required, use an intermediate supply (additional supply) with the aid of a CPX-M-GE-EV-Z.
NOTICE!
The safety function of output channel CH0 is disabled when the intermediate supply CPX-M-GE-EV-Z is
assembled on the right side of interlinking block CPX-M-GE-EV-FVO.
3.2

Connecting the cables and plugs to the manifold block

NOTICE!
Incorrect handling can cause damage to the electronics modules.
Switch off the supply voltages before assembly or installation.
Only switch on the electrical power supplies when the product has been fully assembled and all
installation work is complete.
Ensure that defective cables are replaced immediately.
Actuators are connected to the manifold block. This means that the plugs and cables can remain on
the manifold block when, for example, the electronics module is replaced.
The degree of protection of the module depends on the manifold block as well as on the plugs and
cover caps used. Information can be found on the following pages and in the
appendix è 8.2 Technical data of the manifold blocks.
Use plugs from the Festo product range (è www.festo.com/catalogue).
The max. permitted line length is 200 m.
Festo — CPX-FVDA-P2 — 2018-10b
is no longer available on the right side of interlinking block CPX-M-GE-EV-FVO.
/0 V
is switched to the right of
VAL
VAL
/0 V
is no longer available.
OUT
OUT
57