Function
2.1.9
Connecting Elements
Connection [XF1], [XF2]
1) Housing
Tab. 5 Connection [XF1], [XF2]
Port [XD]
1)
1) The ports XD.0 and XD.1 and also XD.2 and XD.3, respectively, are interconnected in the terminal strip.
Tab. 6 Port [XD]
2.2
Address Assignment
The system CPX-E is composed of a different number of inputs and outputs, depending on the number
and type of modules CPX-E used and the parameterisation of the bus module. The inputs and outputs
are assigned automatically within the system CPX-E. The address assignment (number of allocated
inputs and outputs) on the system CPX-E must be determined prior to commissioning.
•
A maximum of 10 I/O modules + bus module is permitted in one system CPX-E.
•
The address space of a system CPX-E is limited. The bus module provides the system CPX-E with a
maximum address space of 64 bytes for inputs and 64 bytes for outputs.
•
Activated diagnostic functions as well as status bits or the I/O diagnostic interface reduce the size
of the available address space.
2.3
Addressing
2.3.1
Basic Rules for Addressing
–
The address assignment of the inputs does not depend on the address assignment of the outputs.
Festo — CPX-E-PN — 2020-01a
Signal
1
TD+
Transmitted data +
2
TD–
Transmitted data
3
RD+
Received data +
–
4
n.c.
–
5
n.c.
6
RD–
Received data –
–
7
n.c.
–
8
n.c.
Shield
Functional earth
1)
Signal
0
+24 V DC operating voltage supply U
1
2
0 V DC operating voltage supply U
3
–
EL/SEN
EL/SEN
9