Connecting Elements; Address Assignment; Addressing; Basic Rules For Addressing - Festo CPX-E-PN Translation Of The Original Instructions

Bus module
Hide thumbs Also See for CPX-E-PN:
Table of Contents

Advertisement

Function
2.1.9

Connecting Elements

Connection [XF1], [XF2]
1) Housing
Tab. 5 Connection [XF1], [XF2]
Port [XD]
1)
1) The ports XD.0 and XD.1 and also XD.2 and XD.3, respectively, are interconnected in the terminal strip.
Tab. 6 Port [XD]
2.2

Address Assignment

The system CPX-E is composed of a different number of inputs and outputs, depending on the number
and type of modules CPX-E used and the parameterisation of the bus module. The inputs and outputs
are assigned automatically within the system CPX-E. The address assignment (number of allocated
inputs and outputs) on the system CPX-E must be determined prior to commissioning.
A maximum of 10 I/O modules + bus module is permitted in one system CPX-E.
The address space of a system CPX-E is limited. The bus module provides the system CPX-E with a
maximum address space of 64 bytes for inputs and 64 bytes for outputs.
Activated diagnostic functions as well as status bits or the I/O diagnostic interface reduce the size
of the available address space.
2.3

Addressing

2.3.1

Basic Rules for Addressing

The address assignment of the inputs does not depend on the address assignment of the outputs.
Festo — CPX-E-PN — 2020-01a
Signal
1
TD+
Transmitted data +
2
TD–
Transmitted data
3
RD+
Received data +
4
n.c.
5
n.c.
6
RD–
Received data –
7
n.c.
8
n.c.
Shield
Functional earth
1)
Signal
0
+24 V DC operating voltage supply U
1
2
0 V DC operating voltage supply U
3
EL/SEN
EL/SEN
9