Addressing; Basic Rules For Addressing; Addressing Example - Festo CPX-E-EP Translation Of The Original Instructions

Bus module
Hide thumbs Also See for CPX-E-EP:
Table of Contents

Advertisement

Function
The address assignment (number of allocated inputs and outputs) on the system CPX-E must be
determined prior to commissioning.
A maximum of 10 I/O modules + bus module is permitted in one system CPX-E.
The address space of a system CPX-E is limited. The bus module provides the system CPX-E with a
maximum address space of 64 bytes for inputs and 64 bytes for outputs.
Activated diagnostic functions as well as status bits or the I/O diagnostic interface reduce the size
of the available address space.
2.3

Addressing

2.3.1

Basic Rules for Addressing

The address assignment of the inputs does not depend on the address assignment of the outputs.
The numbering goes from left to right.
The bus module counts as a module with 0 inputs and 0 outputs when the status bits and the I/O
diagnostic interface are deactivated.
Activated status bits occupy 8 inputs.
An activated I/O diagnostic interface occupies 16 inputs and 16 outputs.
The inputs and outputs of different module types are assigned separately from each other. The
following sequence applies:
Bus module with status bits or I/O diagnostic interface (if activated via DIL switch)
Analogue modules
Technology modules
Digital modules
2.3.2

Addressing Example

Fig. 4
The address assignment for the system CPX-E presented is shown in è Tab.
12
1 Bus module CPX-E-EP (with status bits)
–Status bits activated
–I/O diagnostic interface deactivated
2 Digital input module CPX-E-16DI
3 Digital output module CPX-E-8DO
4 Digital output module CPX-E-8DO
5 Analogue input module CPX-E-4AI-U-I
6 Analogue output module CPX-E-4AO-U-I
Festo — CPX-E-EP — 2020-01a