Festo CPX-FVDA-P2 Original Instructions Manual page 83

Output module
Hide thumbs Also See for CPX-FVDA-P2:
Table of Contents

Advertisement

Diagnostics and error handling
6.2
Possible error messages of the output module CPX-FVDA-P2
Error no.
Display on the
operator unit
2
[Short circuit]
1)
3
[Wire fracture/
2)
idling current I/O]
5
[Undervoltage in
3)
power supply]
3)
61
[Overvoltage in
power supply]
3)
65
[F_DEST_ADD mis-
match]
66
3)
[F-Communication
fault]
3)
67
[F-Communication
timeout]
1)
68
[Leakage current]
3)
69
[F-Parameter fault] Error in safe parameterisation
Festo — CPX-FVDA-P2 — 2018-10b
Description
Short circuit/overload at output. –
Wire break.
Undervoltage in supply voltage
U
.
VAL
Overvoltage in supply voltage
U
.
VAL
The PROFIsafe address set by
the DIL switch does not correlate
with the setting on the
PROFIsafe master
(F_DEST_ADD).
Error in safe communication.
Timeout during PROFIsafe trans-
mission.
The chronological sequence of
the PROFIsafe communication is
malfunctioning.
Cross-circuit error (shunt error)
at output.
(safety parameterisation inval-
id). PROFIsafe communication
cannot be established.
Error handling
Eliminate short circuit.
Acknowledge and reinteg-
rate the module or output
channel.
Check and, if required,
replace the cables and con-
nected actuators.
Eliminate undervoltage.
Acknowledge and reinteg-
rate the module.
Eliminate overvoltage.
Acknowledge and reinteg-
rate the module.
Check the set address or
F_DEST_ADD parameter.
Correct address or send new
parameters.
Check F-Host.
Acknowledge and reinteg-
rate the module.
Check program in F-Host.
Check communication
paths.
Check timeout (parameter
F_WD_Time).
Acknowledge and reinteg-
rate the module.
Eliminate cross circuit.
Acknowledge and reinteg-
rate the module or output
channel.
Check PROFIsafe paramet-
ers.
Send corrected parameters.
83

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents