Festo CPX-FVDA-P2 Original Instructions Manual page 94

Output module
Hide thumbs Also See for CPX-FVDA-P2:
Table of Contents

Advertisement

Technical appendix
Fig. 37 Maximum permissible load inductivity at the output channels
Functional characteristic values
Module code
Sub-module code
Compatible with fast start-up (FSU)
Start-up time until module ready
Diagnostics of external channel fault
Response time for external channel errors
Response time to switch off command (typ.)
Internal PROFIsafe processing time (T
Tab. 46 Functional characteristic values
Safety characteristics
Safety function
Shutdown schema for each output channel
94
)
DAT
1)
CPX-FVDA-P2
193d (C1h)
8d (08h)
Yes
[s]
 2
<
Periodic inspection
for function
for external supply
for cross circuit
[min]
 1
<
[ms]
 10
<
[ms]
 50
<
CPX-FVDA-P2
Safe shutdown of the output chan-
nels
in accordance with IEC 61508
with SIL 3
in accordance with
EN ISO 13849 with Cat. 3, PL e
in accordance with EN 62061
with SIL CL 3
P- and M-switching
Festo — CPX-FVDA-P2 — 2018-10b