Diagnostics

3.1

Diagnostics by means of LED display

Digital electronic modules
LED displays on digital electronic modules:
Status and error displays by means of LEDs on digital electronic modules
The table below shows the status and error displays on the digital electronic modules.
SF
on
Digital electronic module 4DO DC24V/2A HF (6ES7132-4BD30-0AB0)
Manual, 10/2009, A5E02515335-02
Group error (red)
Status display for output status (green)
Event (LEDs)
1
5
2
6
on
on
on
on
Cause
No configuration or incorrect
module plugged in. There is a
diagnostic message.
Output on channel 0 activated.
Output on channel 1 activated.
Output on channel 2 activated.
Output on channel 3 activated.
Remedy
Check the parameter
assignment. Evaluate the
diagnostics.