Logic Command/Status Words
Appendix D provides the definitions of the Logic Command/Logic
Status words that are used for some products that can be connected to the
ControlNet adapter. If you do not see the Logic Command/Logic Status
for the product that you are using, refer to your product's documentation.
PowerFlex 70 and PowerFlex 700 Drives
Logic Command Word
Logic Bits
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Command Description
x x x
x
* A 0 = Not Stop condition (logic 0) must first be present before a 1 = Start condition will start the drive.
x x
x
x
x x
x x
x Stop
x
Start*
x
Jog
x
Clear
Faults
Direction
Local
Control
MOP
Increment
Accel Rate 00 = No Command
Decel Rate 00 = No Command
Reference
Select
MOP
Decrement
Appendix
0 = Not Stop
1 = Stop
0 = Not Start
1 = Start
0 = Not Jog
1 = Jog
0 = Not Clear Faults
1 = Clear Faults
00 = No Command
01 = Forward Command
10 = Reverse Command
11 = Hold Direction Control
0 = No Local Control
1 = Local Control
0 = Not Increment
1 = Increment
01 = Accel Rate 1 Command
10 = Accel Rate 2 Command
11 = Hold Accel Rate
01 = Decel Rate 1 Command
10 = Decel Rate 2 Command
11 = Hold Decel Rate
000 = No Command
001 = Ref. 1 (Ref A Select)
010 = Ref. 2 (Ref B Select)
011 = Ref. 3 (Preset 3)
100 = Ref. 4 (Preset 4)
101 = Ref. 5 (Preset 5)
110 = Ref. 6 (Preset 6)
111 = Ref. 7 (Preset 7)
0 = Not Decrement
1 = Decrement