Allen-Bradley PowerFlex 755T User Manual

Allen-Bradley PowerFlex 755T User Manual

Powerflex 750-series drives with totalforce control built-in ethernet/ip adapter
Hide thumbs Also See for PowerFlex 755T:
Table of Contents

Advertisement

User Manual
Original Instructions
PowerFlex 750-Series Drives with TotalFORCE Control
Built-in EtherNet/IP Adapter
Catalog Numbers 20G; 20J

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the PowerFlex 755T and is the answer not in the manual?

Questions and answers

Liam Edmonds
February 26, 2025

How can a Powerflex755TL VFD be configured to detect loss of power at the motor (power disconnect at the motor) as a fault and remove the run command to the motor?

1 comments:
Mr. Anderson
February 26, 2025

The Allen-Bradley PowerFlex 755T VFD can be configured to detect a loss of power at the motor and remove the run command by utilizing the Safe Torque Off (STO) function. This function ensures that torque is not applied when required for safety. Additionally, the drive logic command word includes bits for fault detection and control, such as the "Clear Faults" bit, which can be used to respond to power loss conditions. Proper ladder logic programming in the Logix Designer application can also be implemented to monitor motor power loss and execute the required safety actions.

This answer is automatically generated

Summary of Contents for Allen-Bradley PowerFlex 755T

  • Page 1 User Manual Original Instructions PowerFlex 750-Series Drives with TotalFORCE Control Built-in EtherNet/IP Adapter Catalog Numbers 20G; 20J...
  • Page 2: Important User Information

    Important User Information Read this document and the documents listed in the additional resources section about installation, configuration, and operation of this equipment before you install, configure, operate, or maintain this product. Users are required to familiarize themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws, and standards.
  • Page 3 Table of Contents Preface ............13 Conventions Used in This Manual .
  • Page 4 Using Automatic Device Configuration (ADC) ....71 Configure a PowerFlex 755T Drive for ADC ....73 ADC and Logix Memory.
  • Page 5 Table of Contents Explanation of Request and Response Data for Scattered Read Multiple Messaging ......109 Chapter 6 Troubleshooting Viewing Interface Diagnostic Items .
  • Page 6 Logic Command Word ........175 PowerFlex 755T Drives and Bus Logic Status Word .
  • Page 7 PowerFlex 755T Drive Status Indicator Descriptions ........
  • Page 8 Table of Contents DPI Device Object: Instance Attributes ..........145 DPI Parameter Object: Class Code .
  • Page 9 Table of Contents Ethernet Link Object: Services ........... . . 173 Ethernet Link Object: Instances .
  • Page 10 Table of Contents Notes: Rockwell Automation Publication 750COM-UM009A-EN-P - May 2017...
  • Page 11: Preface

    PowerFlex® 755T drives and bus supplies, and how to use it for network communication. To order paper copies of documentation, contact your local Allen-Bradley distributor or Rockwell Automation® sales representative. To find your local Allen-Bradley distributor or sales representative, visit http:// www.rockwellautomation.com/locations.
  • Page 12 PowerFlex 755TM Power and Filter Module Storage Provides detailed installation and usage instructions Hardware Instructions, publication 750-IN106 for this hardware accessory. PowerFlex 755T Module Service Ramp Instructions, Provides detailed usage instructions for the module publication 750-IN108 service ramp. PowerFlex 750-Series Products with TotalFORCE Control...
  • Page 13 Provides declarations of conformity, certificates, and www.rockwellautomation.com/global/certification/ other certification details. overview.page You can view or download publications at http://www.rockwellautomation.com/global/literature-library/overview.page. To order paper copies of technical documentation, contact your local Allen-Bradley distributor or Rockwell Automation sales representative. Rockwell Automation Publication 750COM-UM009A-EN-P - May 2017...
  • Page 14 Preface Notes: Rockwell Automation Publication 750COM-UM009A-EN-P - May 2017...
  • Page 15 Chapter Getting Started The built-in EtherNet/IP interface, on the main control board in PowerFlex® 755T drives, is used for network communication. Topic Page Components Features Dual Ethernet Ports Required Equipment Equipment Shipped with the Drive User-supplied Equipment Choose an Ethernet Switch Safety Precautions Rockwell Automation Publication 750COM-UM009A-EN-P - May 2017...
  • Page 16: Getting Started Components

    Chapter 1 Getting Started Components Components that are shown have the HIM bezel open and the drive cover Item Part Description removed Drive STS Indicator Status Indicates the overall status of Indicator - network communication. See Drive Control Pod Chapter 6, Troubleshooting.
  • Page 17: Dual Ethernet Ports

    16 datalinks to read data to the network from the drive. • Explicit Messaging support. • User-defined fault actions to determine how the built-in EtherNet/IP interface and its host PowerFlex 755T drive respond to the following: – I/O messaging communication disruptions (Comm Flt Action) –...
  • Page 18: Required Equipment

    Equipment Shipped with the Drive Since the EtherNet/IP interface is built in the main control board in the PowerFlex 755T drive, it is always a part of the drive. There are no separate physical installation instructions for the interface. Rockwell Automation Publication 750COM-UM009A-EN-P - May 2017...
  • Page 19: User-Supplied Equipment

    Getting Started Chapter 1 User-supplied Equipment To configure the built-in EtherNet/IP interface, you must supply the following: • A small flat-blade screwdriver for setting the network address switches. • An Ethernet cable (for details, see the EtherNet/IP Media Planning and Installation Manual, ODVA publication 148, available on the ODVA website at http://odva.org/Home/ODVATECHNOLOGIES/...
  • Page 20: Choose An Ethernet Switch

    Chapter 1 Getting Started Choose an Ethernet Switch If the built-in EtherNet/IP interface is used to communicate with a controller that has multicast connections, a managed switch that supports IGMP snooping is suggested. EtherNet/IP implicit (I/O) messaging can be configured to use IP multicast to distribute I/O control data, which is consistent with the CIP-based network Producer/ Consumer model.
  • Page 21: Safety Precautions

    Getting Started Chapter 1 Safety Precautions Read the following safety precautions carefully. ATTENTION: • Risk of injury or equipment damage exists. Only personnel familiar with drive and power products and the associated machinery can plan or implement the installation, start up, configuration. Only qualified personnel can perform subsequent maintenance of the drive by using this built-in interface.
  • Page 22 Chapter 1 Getting Started Notes: Rockwell Automation Publication 750COM-UM009A-EN-P - May 2017...
  • Page 23 Chapter Configure the Interface This chapter provides instructions and information for setting the parameters to configure the built-in EtherNet/IP interface. Topic Page Configuration Tools Setting the IP Address Connecting the Interface to the Network Apply Power Start-up Status Indications Configuring and Verifying Key Drive Parameters Use Interface Parameters to Set the IP Address Using the PowerFlex 20-HIM-A6 or 20-HIM-C6S to Access Parameters Using a BOOTP or DHCP Server...
  • Page 24: Configure The Interface Configuration Tools

    10 or later home.aspx, or online help (installed with the software) (1) CCW release10 requires an additional software updates to add PowerFlex 755T support. It is downloadable from the Product Compatibility and Download Center at: http://compatibility.rockwellautomation.com/Pages/home.aspx Setting the IP Address...
  • Page 25 Configure the Interface Chapter 2 Figure on page 28 and its accompanying table for switch settings and their related descriptions. IMPORTANT When using the interface rotary switches, set the IP address before power is applied because the interface uses the switch settings that it detects when it first receives power.
  • Page 26 Chapter 2 Configure the Interface IMPORTANT Regardless of the method that is used to set the interface IP address, each node on the EtherNet/IP network must have a unique IP address. To change an IP address, you must set the new value and then remove and reapply power to (or reset) the interface.
  • Page 27: Connecting The Interface To The Network

    4. Connect one end of an Ethernet cable to the network. Figure 5 for an example of wiring to an EtherNet/IP network. Figure 5 - Connecting the Ethernet Cable to the Network PowerFlex 755T drives (each with built-in EtherNet/IP interface) Controller Ethernet Switch 5.
  • Page 28: Apply Power

    Chapter 2 Configure the Interface Apply Power ATTENTION: Risk of equipment damage, injury, or death exists. Unpredictable operation can occur if you fail to Verify that parameter settings are compatible with your application. Verify that settings are compatible with your application before power is applied to the drive.
  • Page 29: Start-Up Status Indications

    Configure the Interface Chapter 2 Start-up Status Indications After power is applied, the drive STS (status) indicator and the built-in EtherNet/IP interface ENET, LNK1, and LNK2 status indicators can be monitored via status parameters, HIM status, and the software tool status, if personal protective equipment is worn, they can also be viewed on the front of the drive (Figure...
  • Page 30: Drive And Interface Start-Up Status Indications

    Chapter 2 Configure the Interface Table 1 - Drive and Interface Start-up Status Indications Item Name Color State Description Drive STS Indicator STS (Status) Green Flashing Drive ready but is not running, and no faults are present. Steady Drive is running and no faults are present. Yellow Flashing When running, a type 2 (non-configurable) alarm condition exists –...
  • Page 31: Configuring And Verifying Key Drive Parameters

    Chapter 2 Configuring and Verifying Key Drive Parameters The PowerFlex 755T drive can be separately configured for the command logic and reference functions in various combinations. For example, you could set the drive to have the logic command come from a peripheral or terminal block but have the reference come from the network.
  • Page 32: To Access Parameters

    Chapter 2 Configure the Interface Using the PowerFlex 20-HIM-A6 or 20-HIM-C6S to Access Parameters If your drive has an enhanced PowerFlex 20-HIM-A6 or 20-HIM-C6S HIM, it can be used to access parameters in the interface. 1. Display the Status screen, which is shown on HIM power-up. 2.
  • Page 33 It is not able to communicate with devices on other subnets. • If the PowerFlex 755T gateway address is not set to 0.0.0.0, then it must be set to an address that is on the same subnet as the drive's IP address.
  • Page 34: Using A Bootp Or Dhcp Server

    It is not able to communicate with devices on other subnets. • If the PowerFlex 755T gateway address is not set to 0.0.0.0, then it must be set to an address that is on the same subnet as the drive's IP address.
  • Page 35 Configure the Interface Chapter 2 1. Depending on the type of server (BOOTP or DHCP) being used, set 0:300 - [Net Addr Sel] to either ‘2’ (BOOTP) or ‘3’ (DHCP) respectively. With drive firmware 1.xxx or later Stopped AUTO Value Setting 0.00 Hz Edit Net Addr Sel...
  • Page 36 Chapter 2 Configure the Interface 3. On a computer that is connected to the EtherNet/IP network, start the BOOTP/DHCP software. The BOOTP/DHCP Server dialog box appears. To configure devices on your EtherNet/IP network, you must configure settings in the BOOTP/DHCP software to match the network. 4.
  • Page 37 Configure the Interface Chapter 2 6. Click OK to apply the settings. Devices on the network that issue BOOTP/DHCP requests appear in the BOOTP/DHCP Request History list. 7. In the BOOTP/DHCP Request History list, either double-click the Ethernet Address (MAC) of the interface noted in step 2, or click New in the Relation List.
  • Page 38: Setting The Data Rate

    Chapter 2 Configure the Interface TIP To enable BOOTP or DHCP for an interface that has had BOOTP/DHCP disabled, first select the interface in the Relation List. Then, depending on the type of server, click Enable BOOTP or Enable DHCP and, lastly, reset the interface or power cycle the drive.
  • Page 39: Setting Communication Hierarchy

    Configure the Interface Chapter 2 Setting Communication A hierarchy determines the type of device with which the interface exchanges data. In a Controller hierarchy, the interface exchanges data with the Hierarchy ControlLogix® controller or another communication bridge. When a multicast I/O connection is used or when the interface does not have a valid gateway address, the controller must be on the same IP subnet as the interface to establish an I/O connection.
  • Page 40 When using the controller for speed reference via the interface, set two fields in drive 10:1800 - [VRef A Sel]. a. Set the Port field for the drive (for example, 0 - PowerFlex 755T). b. Set the Parameter field to point to the parameter containing the...
  • Page 41 Configure the Interface Chapter 2 IMPORTANT Always use the datalink parameters in consecutive numerical order. Start with the first parameter. For example, use 0:340…344 to configure five datalinks to read data. Otherwise, the network I/O connection size is larger than necessary, which needlessly increases controller response time and memory usage.
  • Page 42: Setting A Fault Action

    Chapter 2 Configure the Interface Setting a Fault Action By default, when the drive is controlled by the network or receives information from the network; communication is disrupted. The drive responds by faulting, if it is using I/O from the network. Possible causes include that the network cable is disconnected, the controller is idle (in Program mode or faulted), or Explicit Messaging for drive control is disrupted.
  • Page 43: Setting The Fault Configuration Parameters

    Configure the Interface Chapter 2 Changes to these parameters take effect immediately. A reset is not required. If communication is disrupted and then re-established, the drive automatically receives commands over the network again. Setting the Fault Configuration Parameters When, these Port 0:Parameters are set to ‘Send Flt Cfg’: •...
  • Page 44 Chapter 2 Configure the Interface Because the built-in EtherNet/IP interface is part of Port 0, restoring the port defaults also resets other drive configuration settings that are made in Port 0. Follow these steps to restore interface parameters to their default configuration values.
  • Page 45: Viewing The Interface Status Using Parameters

    0:317 - [Net Rate Act 2] The data rate/duplex used by the ENET2 network port on the interface. Updating the Interface The interface firmware is contained within the PowerFlex 755T drive firmware. The interface firmware can be updated over the network. Firmware When updating firmware over the network, you can use the Allen-Bradley®...
  • Page 46 Chapter 2 Configure the Interface Notes: Rockwell Automation Publication 750COM-UM009A-EN-P - May 2017...
  • Page 47 Chapter Configuring the Drive in a Logix System This chapter provides instructions on how to configure an Allen-Bradley® ControlLogix® controller to communicate with a connected PowerFlex® 755T drive. The minimum RSLogix 5000® or Studio 5000® software version that can work with the PowerFlex 755T drives is version 20.
  • Page 48 Chapter 3 Configuring the Drive in a Logix System Establish Communication RSLinx® Classic software, in all its variations (Lite, Gateway, OEM, and so forth), is used to provide a communication link between the computer, network, and controller. RSLinx Classic software requires its network-specific driver to be configured before communication is established with network devices.
  • Page 49 Configuring the Drive in a Logix System Chapter 3 6. Click OK. The ‘Configure Driver:’ dialog box appears. 7. Depending on your application, select either the browse local or remote subnet option. 8. Click OK. The Configure Drivers dialog box reappears with the new driver in the Configured Drivers list.
  • Page 50: System Uploading The Electronic Data Sheet (Eds) File

    ‘Ethernet devices’ or the ‘Remote Devices via Linx Gateway’ RSLinx driver. Uploading the Electronic PowerFlex 755T Series drives have built-in EDS files for RSLinx software to upload and register. Data Sheet (EDS) File 1. Right-click the EtherNet/IP drive that is shown as a yellow question mark or ‘Unrecognized Device’...
  • Page 51: Obtain Add-On Profiles

    Go to http://compatibility.rockwellautomation.com/Pages/home.aspx download the latest drive Add-on Profile for the PowerFlex 755T drive. The Logix Designer application drive Add-on Profiles provide these advantages: • Profiles for specific drives that provide descriptive controller tags for basic control I/O words (logic command/status and reference/ feedback) and datalinks.
  • Page 52: Adding The Bridge To The I/O Configuration

    Chapter 3 Configuring the Drive in a Logix System Figure 9 - Example ControlLogix Controller EtherNet/IP Network IP address 10.91.166.96 ControlLogix Controller IP address 10.91.166.21 PowerFlex 755T drive with built- in EtherNet/IP interface Ethernet Switch Computer with Ethernet Connection Adding the Bridge to the I/O Configuration...
  • Page 53 Configuring the Drive in a Logix System Chapter 3 The Logix Designer application dialog box reappears with the tree view in the left pane. 3. In the tree view, right-click the 1756 Backplane in the I/O Configuration folder and choose New Module. The Select Module Type dialog box appears.
  • Page 54: Add The Drive To The Project

    To transmit data between the controller and the drive, you must add the drive as a child device to the parent Ethernet bridge. In this example, Studio 5000 Logix Designer application software version 30 is used with PowerFlex 755T Add-on Profile version 1.01. See section...
  • Page 55 PowerFlex 755T Add-on Profile. 2. From the list, select the PowerFlex 755T drive. 3. Click Create. After you click Create, the dialogue box may appear. If the drive is on the network, select Create Database from Device. If the drive is not on the network, select Update database from website.
  • Page 56 Device Definition window to update any inconsistencies on the Device Definition window. 4. On the Identity window, edit the following data about the drive. Setting Product Select the type of PowerFlex 755T used. Connected Select the Ethernet connection that is used by the drive. Module Name A name to identify the drive.
  • Page 57: Configure Input And Output Data

    Output tab contains outputs from the controller to the drive. Up to 16 datalink inputs and 16 datalink outputs can be configured for a PowerFlex 755T drive. IMPORTANT Always use the datalink parameters in consecutive numerical order by starting with the first parameter. Otherwise, the network I/O connection is larger than necessary, which needlessly increases response time and memory usage.
  • Page 58 Chapter 3 Configuring the Drive in a Logix System 4. Repeat for the Output tab and select the desired parameters to datalink. 5. In the Requested Packet Interval (RPI) box, set the RPI to the desired value (default is 20.0 milliseconds). This value determines the interval that a controller uses to move data to and from the drive.
  • Page 59 Configuring the Drive in a Logix System Chapter 3 Figure 10 - Controller Input Tags Example Rockwell Automation Publication 750COM-UM009A-EN-P - May 2017...
  • Page 60: Download The Configuration To The Controller

    Chapter 3 Configuring the Drive in a Logix System Figure 11 - Controller Output Tags Example Download the Configuration After adding the bridge and drive to the I/O configuration, download the configuration to the controller. Save the project on your computer. to the Controller 1.
  • Page 61 Configuring the Drive in a Logix System Chapter 3 TIP If a message box reports that Logix Designer application software is unable to go online: Find your controller in the Who Active dialog box. From the Communication menu, choose Who Active. Find and select the controller.
  • Page 62: Correlate The Drive With The Controller

    Chapter 3 Configuring the Drive in a Logix System Correlate the Drive with the Controller Correlate the drive settings to the Logix Designer application project I/O settings so that they match. While online with the controller: 1. In the tree view under I/O Configuration, right-click the drive and choose Properties.
  • Page 63: Updating The Aops And Database Files

    Configuring the Drive in a Logix System Chapter 3 4. Correlation is performed so the configuration in the project matches the configuration in the physical drive. If differences are found, you need to select either ‘Use Project’ or ‘Use Physical’ for each identified item. Check the boxes for your specific needs.
  • Page 64 Chapter 3 Configuring the Drive in a Logix System To determine your AOP version: 1. Left-click on Module Properties icon in the upper left-hand corner of the AOP. 2. Display the AOP version by selecting About Module Profile. The drive AOPs are shipped with the latest drive and peripheral database files. However, new firmware revisions can be released at any time.
  • Page 65: Configuration To Aid In Field-Failure Replacement

    Update Database from Website – Opens a web browser for offline downloads from the product comparability download center (PCDC). Use the Product Search to either search for ‘database’ or search for drive (for example ‘PowerFlex 755T’) and select the desired firmware revision. To access database files, visit the web address: http://compatibility.rockwellautomation.com/Pages/home.aspx Configuration to Aid in Field- Historically, field-failure replacement has been a manually intensive process.
  • Page 66: Using An Ethernet Switch With Dhcp/Bootp Server

    Chapter 3 Configuring the Drive in a Logix System Step Manual Process Automatic Process Manually update drive with Electronic Keying between Logix controller and drive must ControlFLASH™ if necessary. resolve successfully. Configure Firmware Supervisor and use ‘Exact Match’ for Electronic Keying to automatically update the drive / peripheral firmware if needed.
  • Page 67: Using Firmware Supervisor

    Configuring the Drive in a Logix System Chapter 3 Stratix 6000 (1783-EMS…) The Stratix 6000 performs ‘Dynamic IP address Assignment by Port’ per the settings on the DHCP Configuration tab: Stratix 8000 (1783-MS…) / 8300 (1783-RMS…) The Stratix 8000/8300 sets the IP address per the ‘DHCP Persistence’ tab: One IP address is configured for each port on the switch (star topology - one drive per port).
  • Page 68 Chapter 3 Configuring the Drive in a Logix System 1. Verify that ‘Exact Match’ keying is selected in the drive and peripherals’ properties dialog boxes. a. View the drive keying by clicking the General tab. b. Right-click each peripheral on the Drive tab. c.
  • Page 69: Using Automatic Device Configuration (Adc)

    ADC is available with the following software: • Studio 5000 - Logix Designer, Version 21 or later • RSLogix 5000, Version 20 • PowerFlex 755T AOPs, Version 1.xxx or later Rockwell Automation Publication 750COM-UM009A-EN-P - May 2017...
  • Page 70 TIP To identify the drive AOP version you are using, open the AOP, click the icon in the upper left corner of the window and select “About Module Profile”. ADC works with all versions of the PowerFlex 755T drives when the Logix I/O connection is made through the embedded Ethernet port.
  • Page 71: Configure A Powerflex 755T Drive For Adc

    ADC is configured within the AOP Device Definition window of the PowerFlex 755T drives. 1. Open the desired PowerFlex 755T drive in the Logix Designer I/O Configuration folder and click the Device Definition button. Rockwell Automation Publication 750COM-UM009A-EN-P - May 2017...
  • Page 72 Chapter 3 Configuring the Drive in a Logix System 2. Select Automatic Device Configuration in the navigation list. Check the Enable Automatic Device Configuration box to enable ADC for the drive. Default settings are automatically set for ADC. 3. ADC settings can also be adjusted at the port/peripheral level as desired for your application.
  • Page 73 Configuring the Drive in a Logix System Chapter 3 Some peripherals do not use ADC, and the 20-750-S3 Network STO option module is one example. Its configuration is managed by the Safety Controller is downloaded in the Safety Forward open automatically when the safety connection is opened.
  • Page 74: Adc And Logix Memory

    Peripheral Changes When Using ADC The PowerFlex 755T drives and bus supplies check the power peripherals (power modules, LCL filters, precharge modules, and Torque Accuracy Modules) every time it powers up. During power up, the system checks to see if the peripherals are the same and in the same order.
  • Page 75: Special Considerations For 20-750-S1 Safe Speed Module (S1)

    The configuration change must be manually accepted by entering a value of ' A ccept' (1) in 0:91 [Cfg Acknowledge]. IMPORTANT After a power peripheral change is detected, the PowerFlex 755T does not accept downloads from the controller until the configuration change is accepted in 0:91 [Cfg Acknowledge].
  • Page 76 Chapter 3 Configuring the Drive in a Logix System IMPORTANT Firmware Supervisor cannot be used to update the 20-750-S1 module firmware, due to unique upgrade components within its safety core. The firmware can be manually upgraded using ControlFLASH, a 1203-USB Serial Converter, and the appropriate upgrade file.
  • Page 77: Developers Kit Option Cards

    Configuring the Drive in a Logix System Chapter 3 7. Set the SSM Parameter 13 [New Password] to ‘0’ . 8. Set the SSM Parameter 17 [Password Command] to ‘1’ (Change PW). 9. Uninhibit the connection or reconnect the cable. The controller can download the new configuration, including the new password.
  • Page 78: Monitoring Adc Progress

    Chapter 3 Configuring the Drive in a Logix System Method 1 1. Connect via the Ethernet by using a second configuration tool, such as Connected Component Workbench (CCW). 2. Change any unused parameters in the drive and/or peripheral ports. Note the parameter value before and after your change. It is the initial parameter write that causes the Configuration Signature to clear for a particular port.
  • Page 79: Drive Status Indicators - Operational

    Chapter 3 See the PowerFlex Drives with TotalFORCE™ Programming Manual, publication 750-PM100 PowerFlex 755T Drive Status Indicator Descriptions on page 116) for information about the status indicators. An operational drive in a running Logix system has the following status indicator states.
  • Page 80: Logix Control Adc Failure Examples

    Faulted A problem that keeps the controller from connecting to the drive (for example, the device at the IP address that is provided is not a PowerFlex 755T drive). The following are examples of Logix controller ADC ‘failures’ with identified potential issues and associated solutions.
  • Page 81: Configuration Signature

    Configuring the Drive in a Logix System Chapter 3 Table 5 - Logix Control ADC Failure Examples Scenario/Error Probable Cause Potential Solutions ADC doesn’t Required manual steps to ADC is not fully automatic when used with a 20-750-S1 complete when 20- unlock/lock and set the (S1) module.
  • Page 82 Chapter 3 Configuring the Drive in a Logix System Figure 13 shows an example Logix program that monitors the Ethernet connection status to the PowerFlex drive and checks for a Configuration Signature in Port 0 in the drive. If the connection is running (4000 Hex = 16384 Dec), a timer is used to read the Configuration Signature periodically in Port 0 in the drive.
  • Page 83: Best Practices

    Configuring the Drive in a Logix System Chapter 3 Best Practices When using ADC in your control system, adhere to the following recommendations: • To configure a drive, use only the Studio 5000 environment drive AOP. If another tool is used to configure the drive, complete the drive configuration and then upload the configuration to the drive AOP and save your project.
  • Page 84 Chapter 3 Configuring the Drive in a Logix System Notes: Rockwell Automation Publication 750COM-UM009A-EN-P - May 2017...
  • Page 85 PowerFlex drive and sets its reference. I/O connections can also be used to transfer data to and from datalinks in PowerFlex 755T drives. The interface includes the logic command, logic status, reference, feedback, and memory allocation for the generic Ethernet module profile (all as 32-bit words) in the I/O image of the controller.
  • Page 86: Understanding The Controllogix Controller I/O Image

    Chapter 4 Using the I/O in the Ethernet bridge using the RSLogix 5000® / Studio 5000® environment. Additional I/O, if needed, can be set using up to 16 datalinks to write data and/or up to 16 datalinks to read data. When using any combination of these datalinks, add one 32-bit word for each datalink to the basic I/O Input Size and/or Output Size.
  • Page 87: Using Logic Command/Status

    Using the I/O Chapter 4 Table 6 shows the I/O image when using all 32-bit datalinks. Table 6 - ControlLogix I/O Image for PowerFlex 755T Drives (32-bit Logic Command/Status, Reference/Feedback, and Datalinks) DINT Output (Controller to Drive) I/O DINT Input (Drive to Controller) I/O...
  • Page 88: Powerflex755T Drives Example Velocity Reference/Feedback Scaling

    32.5 Hz 32.5 (1) The effects of values less than 0.0 depend on whether the PowerFlex 755T drive uses a bipolar or unipolar direction mode. See the drive documentation for details. (2) For this example, drive 10:1891 - [Velocity Units] is set to Hz.
  • Page 89: Using Datalinks

    Datalinks for PowerFlex 755T peripherals are locked when the peripheral has an I/O connection with a controller. For example, the built-in EtherNet/IP interface on PowerFlex 755T drives only, and option modules such as an encoder or a communication module. When a controller has an I/O connection to the drive, the drive does not allow anything that could change the makeup of the I/O connection in a running system.
  • Page 90: Example Of Ladder Logic Program Information

    PowerFlex 755T drives. See Appendix E, Logic Command/Status Words: PowerFlex 755T drives and Bus Supplies to view details. ControlLogix Controller This section includes information on how to use a ControlLogix controller, and an RSLogix 5000 or Studio5000 drive Add-on Profile.
  • Page 91 Using the I/O Chapter 4 Figure 14 - ControlLogix Program Tags for Drive Add-on Profile Ladder Logic Program Example An example ladder logic program that uses the automatically created descriptive Controller tags and passes their data to the user-defined Program tags is shown in Figure 15 Figure...
  • Page 92 Chapter 4 Using the I/O Figure 16 - ControlLogix Controller Example Ladder Logic Program Using a Drive Add-on Profile for Logic Command/Reference Figure 17 - ControlLogix Controller Example Ladder Logic Program Using a Drive Add-on Profile for Logic Command/Reference for a Converter Rockwell Automation Publication 750COM-UM009A-EN-P - May 2017...
  • Page 93 Chapter Using Explicit Messaging This chapter provides information and examples that explain how to use Explicit Messaging with a ControlLogix® controller to configure and monitor the interface and connected PowerFlex® 755TR, 755TL, 755TM drives, and 755TM Bus Supply. For information on how to use a PLC-5®, SLC™ 500, or MicroLogix™ 1100/ 1400 controller, see Controller Examples for EtherNet/IP Network communication with PowerFlex 750-Drives, publication 750COM-AT001.
  • Page 94: Chapter 5 Using Explicit Messaging About Explicit Messaging

    IMPORTANT PowerFlex 755T drives have Explicit Messaging limitations. Table 8 shows the EtherNet/IP Object Class code compatibilities for these drives. Table 8 - Explicit Messaging Class Code Compatibility with PowerFlex 755T Drive EtherNet/IP Object Class Code Compatibility Explicit Messaging Function Parameter Object 0x0F Not supported.
  • Page 95: Explicit Messaging Compatibility With Powerflex 755T Drive

    Using Explicit Messaging Chapter 5 Table 9 - Explicit Messaging Compatibility with PowerFlex 755T Drive Port Number Host (Drive) Parameters Device Parameters Class 0x93 or 0x9F — — Class 0x93 — Class 0x93 — Class 0x93 Class 0x9F Class 0x93...
  • Page 96: Performing Explicit Messaging

    Chapter 5 Using Explicit Messaging Performing Explicit There are five basic events in the Explicit Messaging process. The details of each step vary depending on the type of controller being used. See the Messaging documentation for your controller. Figure 18 - Explicit Message Process Configure and send Explicit Message Request Complete Explicit...
  • Page 97: Controllogix Controller Examples

    0x9F and format the rest of the message in the same way as these examples. Do not use the Service Type Parameter Read, which accesses the Parameter object (class 0x0F). The Parameter object is not supported in PowerFlex 755T drives.
  • Page 98: Formatting A Message To Read A Single Parameter

    Type other than ‘Custom’ from the pull-down menu, the appropriate hexadecimal value is automatically assigned to the Service Code box, which is dimmed (unavailable). (2) The instance is the parameter number plus the offset for the port. For example, to read 10:3 - [Output Current] of a PowerFlex 755T drive, the instance would be 40960 + 3 = 40963. See...
  • Page 99: Ladder Logic Program To Write A Single Parameter

    A Set Attribute Single message is used to write to a parameter. This write message example writes a value to the 32-bit REAL (floating point) 10: 1915 - [VRef Accel Time 1] in a PowerFlex 755T drive. Table 11 - Example Controller Tags to Write a Single Parameter...
  • Page 100: Formatting A Message To Write A Single Parameter

    Type other than ‘Custom’ from the pull-down menu, the appropriate hexadecimal value is automatically assigned to the Service Code box, which is dimmed (unavailable). (2) The instance is the parameter number plus the offset for the port. For example, to write to a 10:1915 [Vref Accel Time 1] of a PowerFlex 755T drive, the instance would be 40960 + 1915 = 42875.
  • Page 101: Ladder Logic Program To Read Multiple Parameters

    A Scattered Read message is used to read the values of multiple parameters. This read message example reads the values of these floating point parameters (five 32-bit REAL) in a PowerFlex 755T drive: • 10:001 - [Output Frequency] • 10:003 - [Output Current] •...
  • Page 102: Formatting A Message To Read Multiple Parameters

    (3) See Table 8 on page 96 for limitations of PowerFlex 755T drives when using DPI Parameter Object Class code 0x93 or Host DPI Parameter Object Class code 0x9F for Explicit Messaging. (4) In this example, we are reading five 32-bit REAL (floating point) parameters. Each parameter being read requires two contiguous DINT registers. Therefore, a controller tag was created with its Data Type field set to ‘DINT[10]’...
  • Page 103 ControlLogix Controller Example Scattered Read Request Data In this message example, the source tag Scattered Read Request, is used to read the five floating point parameters (32-bit REAL) in the PowerFlex 755T drive. DPI Parameter Object on page 145 (Class code 0x93) or...
  • Page 104: Ladder Logic Program To Write Multiple Parameters

    A Scattered Write message is used to write to multiple parameters. This write message example writes the following values to these floating point (32-bit REAL) parameters in a PowerFlex 755T drive, the values are written as Port Number: Parameter Number - [Parameter Name]...
  • Page 105: Formatting A Message To Write Multiple Parameters

    (4) See Table 8 on page 96 for limitations of PowerFlex 755T drives when using DPI Parameter Object Class code 0x93 or host DPI Parameter Object Class code 0x9F for Explicit Messaging. (5) In this example, we are writing to five 32-bit REAL (floating point) parameters. Each parameter being written to requires two contiguous DINT registers. Therefore, a controller tag was created with its Data Type field set to the name of the UDDT of five interleaved DINTs and REALs.
  • Page 106: Rockwell Automation Publication 750Com-Um009A-En-P - May

    (Scattered_Write_Request) to write new values to these floating point(32-bit REAL) parameters. The values are written as Port Number: Parameter Number - [Parameter Name]. PowerFlex 755T Drive Parameter Write Value 10:1916 - [VRef Accel Time 2] 11.1 Sec 10:1918 - [VRef Decel Time 2] 22.2 Sec...
  • Page 107: Scattered Read Multiple Messaging

    Using Explicit Messaging Chapter 5 Explanation of Request and Response Data for Scattered Read Multiple Messaging The data structures in Table 14 Table 15 use 32-bit words and can accommodate up to 32 parameters in a message. In the Response Message, a parameter number with Bit 31 set indicates that the associated parameter value field contains an error code (parameter number in response data is negative).
  • Page 108: Data Structures For Scattered Write Messages

    Chapter 5 Using Explicit Messaging Table 14 - Data Structures for Scattered Read Messages (continued) Parameter Number Parameter Number Parameter Value Parameter Number Parameter Number Parameter Value Parameter Number Parameter Number Parameter Value Parameter Number Parameter Number Parameter Value Parameter Number Parameter Number Parameter Value When performing a Scattered Write to REAL data type parameters, the REAL...
  • Page 109 Using Explicit Messaging Chapter 5 Table 15 - Data Structures for Scattered Write Messages (continued) Parameter Number Parameter Number Parameter Value Parameter Number Parameter Number Parameter Value Parameter Number Parameter Number Parameter Value Parameter Number Parameter Number Parameter Value Parameter Number Parameter Number Parameter Value Rockwell Automation Publication 750COM-UM009A-EN-P - May 2017...
  • Page 110 Chapter 5 Using Explicit Messaging Notes: Rockwell Automation Publication 750COM-UM009A-EN-P - May 2017...
  • Page 111: Viewing Interface Diagnostic Items

    Chapter Troubleshooting This chapter provides information for diagnosing and troubleshooting potential problems with the interface and network. Topic Page Viewing Interface Diagnostic Items Viewing and Clearing Events Drive Status Indicators ENET Status Indicator LNK1 Status Indicator LNK2 Status Indicator Viewing Interface Diagnostic If you encounter unexpected communication problems, the diagnostic items of the interface can help you or Rockwell Automation®...
  • Page 112 Chapter 6 Troubleshooting Table 16 - Interface Diagnostic Items (continued) Name Description DL To Net Avail The number to network datalinks currently available to the interface. DL Fr Net 01 Val The present value of the respective Host DL From Net xx parameter being transmitted to the drive by this interface.
  • Page 113 Troubleshooting Chapter 6 Table 16 - Interface Diagnostic Items (continued) Name Description HW Addr 1 Decimal value of each byte in the Ethernet hardware (MAC) address of the interface. HW Addr 2 HW Addr 3 255:255:255:255:255:255 HW Addr 4 HW Addr 5 [HW Addr 1] HW Addr 6 [HW Addr 2]...
  • Page 114: Viewing And Clearing Events

    Many events in the event queue occur under normal operation. If you encounter unexpected communication problems, the events can help you or Allen-Bradley® personnel troubleshoot the problem. The following events can appear in the event queue. Table 17 - Interface Diagnostic Items...
  • Page 115 Troubleshooting Chapter 6 Table 17 - Interface Diagnostic Items (continued) Code Event Description DHCP Rebind The interface rebinded its network address lease with the DHCP Server. DHCP Release The interface network address lease expired. Net Sent Reset The interface received a reset command from the network.
  • Page 116: Drive Status Indicators

    The interface is properly connected and transmitting data packets on the network. Steady The interface is properly connected but is not transmitting on the network. (1) See the PowerFlex 755T Programming Manual, publication 750-RM002, for information about this parameter. Rockwell Automation Publication 750COM-UM009A-EN-P - May 2017...
  • Page 117: Enet Status Indicator

    Troubleshooting Chapter 6 ENET Status Indicator Table 19 - ENET Status Indicator Description Status Cause Corrective Action The interface is not powered, the interface is not properly connected • Apply power to the drive. to the network, or the interface needs an IP Address. •...
  • Page 118: Lnk2 Status Indicator

    Chapter 6 Troubleshooting LNK2 Status Indicator Table 21 - LNK2 Status Indicator Descriptions Status Cause Corrective Action The interface is not properly connected to the network. Securely connect the interface to the network by using an Ethernet cable. Also, make sure that the Ethernet cable is correctly connected to the Ethernet connector.
  • Page 119: Understanding The Status Indicators

    Appendix Status Indicators Understanding the Status The interface has four status indicators. They can be viewed with the drive HIM bezel closed or open. Indicators Indicators that are shown with HIM Built-in EtherNet/IP interface indicators are on bezel closed and drive cover installed main control board in drive control pod Item Indicator Name...
  • Page 120: Enet Status Indicator

    Appendix A Status Indicators ENET Status Indicator This red/green bicolor status indicator shows the status of the network connection for the interface, as shown in the following table. Table 22 - ENET Status Indicators Status Cause Corrective Actions The interface is not powered, the •...
  • Page 121: Link Status Indicators

    Status Indicators Appendix A LINK Status Indicators These green status indicators show the status of the individual Ethernet connectors for the adapter that transmit or receive data on the network as shown in the following tables. Table 23 - LNK1 Status Indicator Status Cause Corrective Actions...
  • Page 122 Appendix A Status Indicators Notes: Rockwell Automation Publication 750COM-UM009A-EN-P - May 2017...
  • Page 123: Communication

    Appendix Specifications This appendix presents the specifications for the adapter. Communication Network Protocol EtherNet/IP network Data Rates 10 Mbps full-duplex, 10 Mbps half-duplex, 100 Mbps full-duplex, or 100 Mbps half-duplex Connection Limits 30 TCP connections 16 simultaneous CIP-based network explicit connections plus one exclusive owner I/O connection.
  • Page 124 Appendix B Specifications Notes: Rockwell Automation Publication 750COM-UM009A-EN-P - May 2017...
  • Page 125: How Parameters Are Organized

    PowerFlex 755T. Press the (Folders) key, and use key to scroll to the DEV PARAM folder. • Connected Components Workbench™ software—click Parameters. Select 0 - PowerFlex 755T from the port pull-down list. Rockwell Automation Publication 750COM-UM009A-EN-P - May 2017...
  • Page 126: Parameter List

    Appendix C Interface Parameters Parameter List Icon Descriptions This icon indicates that the parameter value cannot be changed until the drive is stopped. This icon indicates that the parameter cannot be set to DataLink In. This icon indicates that an explicit message write cannot change the parameter value. The parameter value can be changed by using a datalink. Table 25 - Port 0: Parameter List Display Name Values...
  • Page 127 Interface Parameters Appendix C Table 25 - Port 0: Parameter List (continued) Display Name Values Extended Name Description Gateway Cfg 1 Default: 32-bit Integer Gateway Cfg 2 Min/Max: 0/255 Gateway Cfg 3 Gateway Cfg 4 Gateway Configuration n Sets the first, second, third, and fourth byte in the gateway address when parameter [Net Addr Src] is set to 1 ‘Parameters’...
  • Page 128 Appendix C Interface Parameters Table 25 - Port 0: Parameter List (continued) Display Name Values Extended Name Description DL From Net 01 Default: 32-bit Integer DL From Net 02 Min/Max: 0/159999 DL From Net 03 DL From Net 04 DL From Net 05 DL From Net 06 DL From Net 07 DL From Net 08...
  • Page 129 Interface Parameters Appendix C Table 25 - Port 0: Parameter List (continued) Display Name Values Extended Name Description Comm Flt Action Default: 0 = ‘Fault’ 32-bit Integer Communication Fault Action Options: 0 = ‘Fault’ Sets the action that the communication interface and drive take when I/O 1 = ‘Stop’...
  • Page 130 Appendix C Interface Parameters Table 25 - Port 0: Parameter List (continued) Display Name Values Extended Name Description Msg Flt Action Default: 0 = ‘Fault’ 32-bit Integer Message Fault Action Options: 0 = ‘Fault’ Sets the action that the interface and drive take when explicit messaging control (only 1 = ‘Stop’...
  • Page 131 Interface Parameters Appendix C Table 25 - Port 0: Parameter List (continued) Display Name Values Extended Name Description Flt Cfg Ref Default: Real Fault Configuration Reference Min/Max: -220000000/+220000000 Set the reference for the drive if any of the following is true: [Comm Flt Action] is set to 4 ‘Send Flt Cfg’...
  • Page 132 Appendix C Interface Parameters Notes: Rockwell Automation Publication 750COM-UM009A-EN-P - May 2017...
  • Page 133: Supported Data Types

    Appendix EtherNet/IP Objects This appendix presents information about the EtherNet/IP objects that can be accessed using explicit messages. For information on the format of explicit messages and example ladder logic programs, see Chapter 5, Using Explicit Messaging. Object Class Code Page Object Class Code...
  • Page 134: Identity Object

    Total number of instances Table 31 - Identity Objects: Instance Attributes Attribute ID Access Rule Name Data Type Description Vendor ID UINT 1 = Allen-Bradley® Device Type UINT Product Code UINT Number that identifies the product name and rating Revision:...
  • Page 135: Assembly Object

    EtherNet/IP Objects Appendix D Table 31 - Identity Objects: Instance Attributes (continued) Attribute ID Access Rule Name Data Type Description Status UINT Bit 0 = Owned Bit 8 = Minor recoverable fault Bit 10 = Major recoverable fault Serial Number UDINT Unique 32-bit number Product Name...
  • Page 136: Pccc Object

    Appendix D EtherNet/IP Objects Table 36 - Assembly Object: Instance Attributes Attribute ID Access Rule Name Data Type Description Number of Members UINT Member List ARRAY of STRUCT: UINT Size of member data UINT Size of member path Packed EPATH Member path Conditional Data...
  • Page 137: Pccc Object: Message Structure For Execute_Pccc

    EtherNet/IP Objects Appendix D Table 39 - PCCC Object: Message Structure for Execute_PCCC Request Response Name Data Type Description Name Data Type Description Length USINT Length of requestor ID Length USINT Length of requestor ID Vendor UINT Vendor number of requestor Vendor UINT Vendor number of requestor...
  • Page 138: N-File Descriptions (All N-Files Are 16-Bit Integers)

    Appendix D EtherNet/IP Objects Table 41 - PCCC Object: EtherNet/IP Interface Supports (continued) Description 0x0F 0xA9 SLC 500 protected typed write with 2 address fields 0x0F 0x00 Word range read 0x0F 0x01 Word range write For more information regarding PCCC commands, see the DF1 Protocol and Command Set Reference Manual, publication 1770- 6.5.16.
  • Page 139 EtherNet/IP Objects Appendix D Table 42 - N-File Descriptions (continued)(All N-files are 16-Bit integers) N-File Description N45:18 DL From Net 08 (least significant) DL To Net 08 (least significant) N45:19 DL From Net 08 (most significant) DL To Net 08 (most significant) N45:20 DL From Net 09 (least significant) DL To Net 09 (least significant)
  • Page 140: Dpi Device Object

    Appendix D EtherNet/IP Objects DPI Device Object Table 43 - DPI Device Object: Class Code Hexadecimal Decimal 0x92 Table 44 - DPI Device Object: Service Service Code Implemented for: Service Name Class Instance 0x0E Get_Attribute_Single 0x10 Set_Attribute_Single Table 45 - DPI Device Object: Instances Instances Device Example...
  • Page 141: Dpi Device Object: Nonvolatile Class Attributes

    USINT Identification of variations. Configuration Text STRING[16] Text identifying a variation of a family device. Brand Code UINT 0x0001 = Allen-Bradley NVS Checksum UINT Checksum of the nonvolatile storage in a device. Class Revision UINT 2 = DPI Character Set Code...
  • Page 142 Appendix D EtherNet/IP Objects Table 46 - DPI Device Object: Nonvolatile Class Attributes (continued) Attribute Access Name Data Type Description Rule Date of Manufacture STRUCT of: UINT Year USINT Month USINT Product Revision STRUCT of: USINT Major Firmware Release USINT Minor Firmware Release Serial Number UDINT...
  • Page 143: Dpi Parameter Object

    EtherNet/IP Objects Appendix D Table 47 - DPI Device Object: Instance Attributes Attribute ID Access Name Data Type Description Rule Component Name STRING[32] Name of the component Component Firmware STRUCT of: Revision USINT Major Revision USINT Minor Revision Component Serial UDINT Value between 0x00000000 and Number...
  • Page 144: Dpi Parameter Object: Class Attributes

    Appendix D EtherNet/IP Objects Table 50 - DPI Parameter Object: Class Attributes Attribute Access Name Data Type Description Rule Number of Instances UINT Number of parameters in the device Write Protect UINT 0 = Password disabled Password n = Password value NVS Command Write USINT 0 = No Operation...
  • Page 145: Dpi Parameter Object: Instance Attributes

    EtherNet/IP Objects Appendix D Table 51 - DPI Parameter Object: Instance Attributes Attribute ID Access Name Data Type Description Rule DPI Offline Read Full STRUCT of: BOOL[32] Descriptor CONTAINER Offline minimum value CONTAINER Offline maximum value CONTAINER Offline Default value STRING[16] Parameter name STRING[4]...
  • Page 146 Appendix D EtherNet/IP Objects Table 51 - DPI Parameter Object: Instance Attributes (continued) Attribute ID Access Name Data Type Description Rule DPI Read Basic STRUCT of: BOOL[32] Descriptor (see page 150) CONTAINER Parameter value CONTAINER Minimum value CONTAINER Maximum value CONTAINER Default value STRING[16]...
  • Page 147 EtherNet/IP Objects Appendix D Table 51 - DPI Parameter Object: Instance Attributes (continued) Attribute ID Access Name Data Type Description Rule International DPI Struct of: Online Read Full BOOL[32] Descriptor CONTAINER Parameter value CONTAINER Online minimum value CONTAINER Online maximum value CONTAINER Online default value UINT...
  • Page 148: Dpi Parameter Object: Descriptor Attributes

    Appendix D EtherNet/IP Objects Table 52 - DPI Parameter Object: Descriptor Attributes Name Description Data Type (Bit 1) Right bit is least significant bit (0). 000 = USINT used as an array of Boolean Data Type (Bit 2) 001 = UINT used as an array of Boolean Data Type (Bit 3) 010 = USINT (8-bit integer) 011 = UINT (16-bit integer)
  • Page 149: Dpi Parameter Object: Extended Descriptor Attributes

    EtherNet/IP Objects Appendix D Table 52 - DPI Parameter Object: Descriptor Attributes (continued) Name Description Writable ENUM ENUM text: 0 = Read Only, 1 = Read/Write Not a Link Source 0 = Can be the source end of a link. 1 = Cannot be the source end of a link.
  • Page 150: Formulas For Converting

    Appendix D EtherNet/IP Objects Table 53 - DPI Parameter Object: Extended Descriptor Attributes (continued) Name Description Uses Rating Table This parameter has rating-dependent defaults and limits that can be obtained from Object the Rating Table Object. The Offline Read Full includes the default value for the smallest rating and limits.
  • Page 151: Dpi Parameter Object: Common Services

    EtherNet/IP Objects Appendix D Table 54 - DPI Parameter Object: Common Services Service Code Implemented for: Service Name Class Instance 0x0E Get_Attribute_Single 0x10 Set_Attribute_Single Table 55 - DPI Parameter Object Specific Services Service Code Implemented for: Service Name Allocation Size (in bytes) Class Instance Par.
  • Page 152: Dpi Fault Object

    Appendix D EtherNet/IP Objects DPI Fault Object Table 58 - DPI Fault Object: Class Code Hexadecimal Decimal 0x97 Products such as PowerFlex drives use this object for faults. Option modules use this object for events. Table 59 - DPI Fault Object: Services Service Code Implemented for: Service Name...
  • Page 153: Dpi Fault Object: Class Attributes

    EtherNet/IP Objects Appendix D Table 61 - DPI Fault Object: Class Attributes Attribute ID Access Rule Name Data Type Description Class Revision UINT Revision of object Number of Instances UINT Maximum number of faults/events that the device can record in its queue. Fault Command Write USINT 0 = No Operation...
  • Page 154: Dpi Alarm Object

    Appendix D EtherNet/IP Objects DPI Alarm Object Table 63 - DPI Alarm Object: Class Code Hexadecimal Decimal 0x98 Products such as PowerFlex drives use this object for alarms or warnings. Option Modules do not support this object. Table 64 - DPI Alarm Object: Services Service Code Implemented for: Service Name...
  • Page 155: Dpi Alarm Objects: Instance Attributes

    EtherNet/IP Objects Appendix D Table 67 - DPI Alarm Objects: Instance Attributes Attribute Access Rule Name Data Type Description Full/All Information STRUCT of UINT Alarm code STRUCT of: Alarm source USINT DPI port USINT DPI Device Object STRING[16] Alarm text STRUCT of: Alarm time stamp LWORD...
  • Page 156: Dpi Diagnostic Object

    Appendix D EtherNet/IP Objects DPI Diagnostic Object Table 68 - DPI Diagnostic Object: Class Code Hexadecimal Decimal 0x99 Table 69 - DPI Diagnostic Object: Services Service Code Implemented for: Service Name Class Instance 0x0E Get_Attribute_Single 0x10 Set_Attribute_Single Table 70 - DPI Diagnostic Object: Instances Instances Device Example...
  • Page 157: Dpi Time Object

    EtherNet/IP Objects Appendix D Table 72 - DPI Diagnostic Object: Instance Attributes Attribute ID Access Rule Name Data Type Description Full/All Information STRUCT of: BOOL[32] Descriptor (see page 150) CONTAINER Value CONTAINER Minimum value CONTAINER Maximum value CONTAINER Default value UINT Pad Word UINT...
  • Page 158: Dpi Time Object: Services

    Appendix D EtherNet/IP Objects Table 74 - DPI Time Object: Services Service Code Implemented for: Service Name Class Instance 0x0E Get_Attribute_Single 0x10 Set_Attribute_Single Table 75 - DPI Time Object: Instances Instances Device Example Description (Hex.) (Dec.) 0x0000…0x0FFF 0…4095 Host Drive Class Attributes (Drive) 0x1000…0x1FFF 4096…8191...
  • Page 159: Dpi Time Object: Instance Attributes

    EtherNet/IP Objects Appendix D Table 76 - DPI Time Object: Class Attributes (continued) Attribute ID Access Rule Name Data Type Description Get/Set Active Time Zone ID UINT The ID field of the Time Zone List structure for the desired time zone. Active Time Zone Data Struct of: Standard bias...
  • Page 160 Appendix D EtherNet/IP Objects Table 77 - DPI Time Object: Instance Attributes (continued) Attribute Access Name Data Type Description Rule International Read Full Struct of: STRINGN International timer text. STRUCT Timer value. BOOL[16] Timer descriptor. International Timer Text STRINGN Name of this timer. Clock Status BOOL[32] Identifies clock status.
  • Page 161: Host Dpi Parameter Object

    EtherNet/IP Objects Appendix D Host DPI Parameter Object Table 78 - Host DPI Parameter Object: Class Code Hexadecimal Decimal 0x9F To access ‘Device’ parameters, use the DPI Parameter Object (Class Code 0x93). Table 79 - Host DPI Parameter Object: Instances Instances Device Example...
  • Page 162: Host Dpi Parameter Object: Instance Attributes

    Appendix D EtherNet/IP Objects Table 80 - Host DPI Parameter Object: Class Attributes (continued) Attribute ID Access Rule Name Data Type Description Class Revision UINT 2 = DPI First Parameter Processing Error UINT The first parameter that has been written with a value outside of its range. A ‘0’...
  • Page 163 EtherNet/IP Objects Appendix D Table 81 - Host DPI Parameter Object: Instance Attributes (continued) Attribute ID Access Rule Name Data Type Description Get/Set DPI Link USINT[3] Link (parameter or function block that is the source of the value). (0 = no link) Help Object Instance UINT ID for help text for this parameter...
  • Page 164 Appendix D EtherNet/IP Objects Table 81 - Host DPI Parameter Object: Instance Attributes (continued) Attribute ID Access Rule Name Data Type Description International DPI Online Struct of: Read Full BOOL[32] Descriptor CONTAINER Parameter value CONTAINER Online minimum value CONTAINER Online maximum value CONTAINER Online default value UINT...
  • Page 165: Host Dpi Parameter Object: Descriptor Attributes

    EtherNet/IP Objects Appendix D Table 82 - Host DPI Parameter Object: Descriptor Attributes Name Description Data Type (Bit 1) Right bit is least significant bit (0). 000 = USINT used as an array of Boolean Data Type (Bit 2) 001 = UINT used as an array of Boolean Data Type (Bit 3) 010 = USINT (8-bit integer) 011 = UINT (16-bit integer)
  • Page 166: Host Dpi Parameter Object: Extended Descriptor Attributes

    Appendix D EtherNet/IP Objects Table 82 - Host DPI Parameter Object: Descriptor Attributes (continued) Name Description Not a Link Source 0 = Can be the source end of a link. 1 = Cannot be the source end of a link. Enhanced Bit ENUM Parameter supports enhanced bit ENUMs.
  • Page 167: Formulas For Converting

    EtherNet/IP Objects Appendix D Table 83 - Host DPI Parameter Object: Extended Descriptor Attributes (continued) Name Description Uses Rating Table Object This parameter has rating-dependent defaults and limits that can be obtained from the Rating Table Object. The Offline Read Full includes the default value for the smallest rating and limits. These limits accommodate the full range of values that are allowed in the family of devices using this particular combination of Family Code and Config Code.
  • Page 168: Host Dpi Parameter Object: Object Specific Services

    Appendix D EtherNet/IP Objects Table 85 - Host DPI Parameter Object: Object Specific Services Service Code Implemented for: Service Name Allocation Size (in bytes) Class Instance Par. Number Par. Value 0x4D Get_Attributes_Scattered 0x4E Set_Attributes_Scattered Table 86 - Get_Attributes_Scattered and Set_Attributes_Scattered Name Data Type Description...
  • Page 169: Tcp/Ip Interface Object

    EtherNet/IP Objects Appendix D TCP/IP Interface Object Table 88 - TCP/IP Interface Object: Class Code Hexadecimal Decimal 0xF5 Table 89 - TCP/IP Interface Object: Services Service Code Implemented for: Service Name Class Instance 0x0E Get_Attribute_Single 0x10 Set_Attribute_Single The interface supports one instance of the TCP/IP Interface object. Table 90 - TCP/IP Interface Object: Instances Number Description...
  • Page 170 Appendix D EtherNet/IP Objects Table 92 - TCP/IP Interface Object: Instance Attributes (continued) Attribute ID Access Rule Name Data Type Description Physical Link Object STRUCT of: UINT Path size Padded EPATH Path Interface Configuration STRUCT of: UDINT Interface IP address UDINT Interface subnet mask UDINT...
  • Page 171: Ethernet Link Object

    EtherNet/IP Objects Appendix D Ethernet Link Object Table 93 - Ethernet Link Object: Class Code Hexadecimal Decimal 0xF6 Table 94 - Ethernet Link Object: Services Service Code Implemented for: Service Name Class Instance 0x0E Get_Attribute_Single 0x4C Get_and_Clear 0x10 Set_Attribute_Single The adapter supports one instance of the TCP/IP Interface object. Table 95 - Ethernet Link Object: Instances Number Description...
  • Page 172: Rockwell Automation Publication 750Com-Um009A-En-P - May

    Appendix D EtherNet/IP Objects Table 97 - Ethernet Link Object: Instance Attributes (continued) Attribute ID Access Rule Name Data Type Description Media Counters STRUCT of: RX = Received, TX = Transmitted UDINT RX frames not having integral number of octets long UDINT RX frames not passing FCS check UDINT...
  • Page 173: Drive Products

    Appendix Logic Command/Status Words: PowerFlex 755T Drives and Bus Supplies This appendix presents the definitions of the logic command and logic status words that are used for PowerFlex® 755T drives and bus supplies. Drive Products Here are the logic command and logic status words for PowerFlex 755TM common-bus inverters, PowerFlex 755TR, and 755TL drives.
  • Page 174: Logic Status Word

    Appendix E Logic Command/Status Words: PowerFlex 755T Drives and Bus Supplies Table 98 - Logic Command Word (continued) Logic Bit Command Description Ref Select 000 = No Command 001 = Ref A Select (10:1800) 010 = Ref B Select (10:1801)
  • Page 175 Logic Command/Status Words: PowerFlex 755T Drives and Bus Supplies Appendix E Table 99 - Logic Status Word (continued) Logic Bit Status Description Manual 0 = Manual Mode Not Active 1 = Manual Mode Active Spd Ref ID 00000 = Reserved...
  • Page 176: Bus Supply Products

    Appendix E Logic Command/Status Words: PowerFlex 755T Drives and Bus Supplies Table 99 - Logic Status Word (continued) Logic Bit Status Description At Zero Speed 0 = Not at Zero Speed 1 =At Zero Speed At Home 0 = Not at Home...
  • Page 177: Logic Status Word

    Logic Command/Status Words: PowerFlex 755T Drives and Bus Supplies Appendix E Logic Status Word Table 101 - Logic Status Words Logic Bit Status Description Ready 0 = Not Ready to Run 1 = Ready to Run Reserved Auto Restart Active...
  • Page 178 Appendix E Logic Command/Status Words: PowerFlex 755T Drives and Bus Supplies Table 101 - Logic Status Words (continued) Enable On 0 = Converter is not being enabled by digital input 1 = Digital input is configured to enable the line-side...
  • Page 179: Glossary

    Glossary The following terms and abbreviations are used throughout this manual. For definitions of terms that are not listed here, refer to the Allen-Bradley® Industrial Automation Glossary, publication AG-7.1. Adapter Devices such as drives, controllers, and computers usually require a network communication adapter to provide a communication interface between them and a network such as EtherNet/IP.
  • Page 180 Datalinks A datalink is a type of pointer that is used by PowerFlex 755T drives to transfer data to and from the controller. Datalinks allow specified parameter values to be accessed or changed without using explicit messages.
  • Page 181 EDS (Electronic Data Sheet) Files Simple text files that are used by network configuration tools to describe products so that you can easily commission them on a network. EDS files describe a product device type and revision. EDS files for many Allen-Bradley products can be found at http://www.ab.com/networks/eds.
  • Page 182 DHCP server. HIM (Human Interface Module) A device that can be used to configure and control a drive. The PowerFlex 20- HIM-A6 or 20-HIM-C6S HIM can be used to configure PowerFlex 755T drives and their connected peripherals. Hold Last When communication is disrupted (for example, a cable is disconnected), the interface and its connected drive can respond by holding last.
  • Page 183 The interface reads the values of these parameters only at power-up. Logic Command/Logic Status The logic command is used to control the PowerFlex 755T drive (for example, start, stop, and direction). It consists of one 32-bit word of output to the interface from the network.
  • Page 184 Glossary RSLogix 5000 Software RSLogix® software is a tool to configure and monitor controllers to communicate with connected devices. It is a 32-bit application that runs on various Windows operating systems. Information about RSLogix software can be found at http://www.software.rockwell.com/rslogix. See also Studio 5000 environment.
  • Page 185 32-bit REAL parameter data for write and read values then display them in human readable format). Update The process of updating firmware in a device. The device can be updated using various Allen-Bradley software tools. See Updating the Interface Firmware on page 47 for more information.
  • Page 186 Glossary Notes: Rockwell Automation Publication 750COM-UM009A-EN-P - May 2017...
  • Page 187: Index

    85 I/O Messaging 87 configuration 21 timeout attribute 117 configuration signature 83 classes of IP addresses 184 configure PowerFlex 755T 73 Comm Flt Action (No. 360) 131 definition 19 communication bridge, see scanner electronic keying 58 communications module, see adapter failures ADC 82 …...
  • Page 188: Rockwell Automation Publication 750Com-Um009A-En-P - May

    116 network example 20 explicit messaging DHCP (Dynamic Host Configuration Protocol) about 96 definition 182 compatibility with PowerFlex 755T 97 free server application 182 configuring for ControlLogix controller 99 using 36 definition 183 using an ethernet switch 68 performing 98...
  • Page 189 Index hardware address Logic Command/Status definition 184 bit definitions for PowerFlex 750-Series in diagnostic item 115 drives 175 on label on main control board 37 definition 185 HIM (Human Interface Module) in I/O image for ControlLogix controller 88 using 89 accessing parameters with 34 definition 184 features 18...
  • Page 190 Index Port 0 Parameters status indicators Comm Flt Action (No. 360) 131 definition 118 DL From Net nn (No. 321…336) 130 descriptions 121 DL To Net nn (No. 340…355) 130 drive operational 81 DLs From Net Act (No. 356) 130 ENET 122 DLs To Net Act (No.
  • Page 192: Rockwell Automation Support

    Rockwell Automation maintains current product environmental information on its website at http://www.rockwellautomation.com/rockwellautomation/about-us/sustainability-ethics/product-environmental-compliance.page. Allen-Bradley, CompactLogix, Connected Components Workbench, ControlLogix, ControlFLASH, DPI, MicroLogix, PLC-5, PowerFlex, Rockwell Software, Rockwell Automation, RSLinx, RSLogix, RSLogix 5000, SLC, Stratix, Studio 5000, Studio 5000 Logix Designer, and TotalFORCE are trademarks of Rockwell Automation, Inc. Trademarks not belonging to Rockwell Automation are property of their respective companies.

This manual is also suitable for:

Powerflex 755tlPowerflex 755trPowerflex 755tm

Table of Contents

Save PDF