Settings - Siemens SIPROTEC 4 Manual

Voltage and frequency protection
Hide thumbs Also See for SIPROTEC 4:
Table of Contents

Advertisement

E.2

Settings

Addresses which have an appended "A" can only be changed with DIGSI, under "Additional Settings".
Addr.
Parameter
0
FLEXIBLE FUNC.
0
OPERRAT. MODE
0
MEAS. QUANTITY
0
MEAS. METHOD
0
PICKUP WITH
0
VOLTAGE
0
VOLTAGE SYSTEM
0
P.U. THRESHOLD
0
P.U. THRESHOLD
0
P.U. THRESHOLD
0
P.U. THRESHOLD
0
P.U. THRESHOLD
0
P.U. THRESHOLD
0
P.U. THRESHOLD
0
T TRIP DELAY
0A
T PICKUP DELAY
0A
T DROPOUT DELAY
0A
BLK.by Vol.Loss
SIPROTEC 4, 7RW80, Manual
C53000-G1140-C233-4, Edition 07.2018
Function
Setting Options
Flx
OFF
ON
Alarm Only
Flx
3-phase
1-phase
no reference
Flx
Please select
Voltage
Frequency
df/dt rising
df/dt falling
Binray Input
dV/dt rising
dV/dt falling
Flx
Fundamental
True RMS
Positive seq.
Negative seq.
Zero sequence
Ratio I2/I1
Flx
Exceeding
Dropping below
Flx
Please select
Va-n
Vb-n
Vc-n
Va-b
Vb-c
Vc-a
Vn
Vx
Flx
Phase-Phase
Phase-Ground
Flx
2.0 .. 260.0 V
Flx
2.0 .. 200.0 V
Flx
40.00 .. 60.00 Hz
Flx
50.00 .. 70.00 Hz
Flx
0.10 .. 20.00 Hz/s
Flx
2.0 .. 260.0 V
Flx
4 .. 100 V/s
Flx
0.00 .. 3600.00 sec
Flx
0.00 .. 60.00 sec
Flx
0.00 .. 60.00 sec
Flx
NO
YES
Functions, Settings, Information
Default Setting
Comments
OFF
Flexible Function
3-phase
Mode of Operation
Please select
Selection of Measured
Quantity
Fundamental
Selection of Measurement
Method
Exceeding
Pickup with
Please select
Voltage
Phase-Phase
Voltage System
110.0 V
Pickup Threshold
110.0 V
Pickup Threshold
51.00 Hz
Pickup Threshold
61.00 Hz
Pickup Threshold
5.00 Hz/s
Pickup Threshold
110.0 V
Pickup Threshold
60 V/s
Pickup Threshold
1.00 sec
Trip Time Delay
0.00 sec
Pickup Time Delay
0.00 sec
Dropout Time Delay
YES
Block in case of Meas.-
Voltage Loss
E.2 Settings
217