Siemens SIPROTEC 4 Manual page 116

Voltage and frequency protection
Hide thumbs Also See for SIPROTEC 4:
Table of Contents

Advertisement

Functions
2.13 Breaker Control
Device Status Check (set = actual): The switching command is rejected, and an error indication is
displayed if the circuit breaker is already in the set position. (If this check is enabled, then it works
whether interlocking, e.g. zone controlled, is activated or deactivated.) This condition is checked in both
interlocked and non-interlocked status modes.
System Interlocking: To check the power system interlocking, a local command is transmitted to the
central unit with Switching Authority = LOCAL. A switching device that is subject to system interlocking
cannot be switched by DIGSI.
Zone Controlled / Bay Interlocking: Logic links in the device which were created via CFC are interrogated
and considered during interlocked switching.
Blocking by Protection: Switch-ON commands are rejected with interlocked switches, as soon as one of
the protection functions of the unit has opened a fault case. The OPEN-command, by contrast, can
always be executed.
Double Operation Block: Parallel switching operations are interlocked against one another; while one
command is processed, a second cannot be carried out.
Switching Authority LOCAL: A control command from the user interface of the device (command with
command source LOCAL) is only allowed if the Key Switch (by configuration) is set to LOCAL.
Switching Authority DIGSI: Switching commands that are issued locally or remotely via DIGSI (command
with command source DIGSI) are only allowed if remote control is admissible for the device (by configu-
ration). If a DIGSI-PC communicates with the device, it deposits here its virtual device number (VD). Only
commands with this VD (when Switching Authority = REMOTE) will be accepted by the device. Remote
switching commands will be rejected.
Switching authority REMOTE: A remote switch command (command with source REMOTE) is only
allowed if remote control is enabled at the device (by configuration).
Control Logic using CFC
For bay interlocking, a release logic can be created using CFC. Via specific release conditions the information
"released" or "bay interlocked" are available (e.g. object "52 Close" and "52 Open" with the data values: ON/
OFF).
Switching Authority
The interlocking condition "Switching Authority" serves for determining the switching authority. It enables the
user to select the authorized command source. For devices with operator panel, the following switching
authority ranges are defined in the following priority sequence:
LOCAL
DIGSI
REMOTE
The "Switching authority" object serves for interlocking or enabling LOCAL control but not REMOTE or DIGSI
commands. With a 7RW80, the switching authority can be changed between "REMOTE" and "LOCAL" on the
operator panel after having entered the password or by means of CFC also via binary inputs and a function
key.
The "Switching authority DIGSI" is used for interlocking and allows commands to be initiated using DIGSI.
Commands are allowed for both a remote and a local DIGSI connection. When a (local or remote) DIGSI PC
logs on to the device, it enters its Virtual Device Number (VD). The device only accepts commands having that
VD (with switching authority = OFF or REMOTE). When the DIGSI PC logs off, the VD is cancelled.
Commands are checked for their source SC and the device settings, and compared to the information set in
the objects "Switching authority" and "Switching authority DIGSI".
Configuration
Switching authority available
Switching authority available DIGSI
Specific device (e.g. switching device)
116
y/n (create appropriate object)
y/n (create appropriate object)
Switching authority LOCAL (check for Local status): y/n
SIPROTEC 4, 7RW80, Manual
C53000-G1140-C233-4, Edition 07.2018