Setting Notes - Siemens SIPROTEC 4 Manual

Voltage and frequency protection
Hide thumbs Also See for SIPROTEC 4:
Table of Contents

Advertisement

Functions
2.4 Load Restoration
[7rw80-monitor-log-bsp-20100525, 1, en_US]
Figure 2-10

Setting Notes

2.4.2
General
The load restoration is active, if Load Restore = Enabled has been set at address 155 during configuration.
If the function is not required Disabled is set.
The various elements of the load restoration are configured ON or OFF at addresses 5520, 5540, 5560 and
5580.
54
Load Restoration – Blocking and Monitoring, Example
SIPROTEC 4, 7RW80, Manual
C53000-G1140-C233-4, Edition 07.2018