Figure 2-2
Undervoltage Protection 27
2.2.3
Funktion
Undervoltage protection consists of three elements (27-1 PICKUP, 27-2 PICKUP, 27 Vp<). Therefore, trip-
ping can be time-graded depending on how severe voltage collapses are. Voltage thresholds and time delays
can be set individually for both elements 27-1 PICKUP and 27-2 PICKUP.
Additionally the element27 Vp< allows the definition of a user defined tripping curve with 20 value pairs
(voltage/ time). Parameterization is done via DIGSI.
SIPROTEC 4, 7RW80, Manual
C53000-G1140-C233-4, Edition 07.2018
Logic diagram of the overvoltage protection
Functions
2.2 Voltage Protection 27, 59