Functions
2.12 Auxiliary Functions
2.12.6.3
Information List
No.
Information
-
OpHour>
272
SP. Op Hours>
2.12.7
Energy Metering
Die Energiezähler werden über Binäreingangsimpulse gemessen.
2.12.7.1
Setting Notes
Setting of parameter for meter resolution
Parameter 8315 MeterResolution allows increasing the resolution of the energy metered values by the
Factor 10 or Factor 100 compared to the Standard setting.
2.12.7.2
Settings
Addr.
Parameter
8315
MeterResolution
2.12.7.3
Information List
No.
Information
-
Meter res
888
Wp(puls)
889
Wq(puls)
Commissioning Aids
2.12.8
In test mode or during commissioning, the device information transmitted to a central or storage device can
be influenced. There are tools available for testing the system interface (port B) and the binary inputs and
outputs of the device.
Applications
•
Test Mode
•
Commissioning
Prerequisites
In order to be able to use the commissioning aids described in the following, the device must be connected to
a control center via port B.
Functional Description
2.12.8.1
Influencing Information to the Control Center During Test Mode
Some of the available protocols allow for identifying all messages and measured values transmitted to the
control center with "Test Mode" as the message cause while the device is tested on site. This identification
110
Type of
Comments
Informa-
tion
LV
Operating hours greater than
OUT
Set Point Operating Hours
Setting Options
Standard
Factor 10
Factor 100
Type of
Comments
Informa-
tion
IntSP_Ev
Reset meter
PMV
Pulsed Energy Wp (active)
PMV
Pulsed Energy Wq (reactive)
Default Setting
Comments
Standard
Meter resolution
C53000-G1140-C233-4, Edition 07.2018
SIPROTEC 4, 7RW80, Manual