Siemens SIPROTEC 4 Manual page 222

Voltage and frequency protection
Hide thumbs Also See for SIPROTEC 4:
Table of Contents

Advertisement

Functions, Settings, Information
E.2 Settings
Addr.
Parameter
5424
FCT 81-4 O/U
5501
LR t Monitor
5502
LR Max. Cycles
5520
LR1
5521
LR1 Start
5522
LR1 Start
5523
LR1 Pickup
5524
LR1 t pickup
5525
LR1 Dropout
5526
LR1 t dropout
5527
LR1 t CB Close
5528
LR1 after 81-1
5529
LR1 after 81-2
5530
LR1 after 81-3
5531
LR1 after 81-4
5540
LR2
5541
LR2 Start
5542
LR2 Start
5543
LR2 Pickup
5544
LR2 t pickup
5545
LR2 Dropout
5546
LR2 t dropout
5547
LR2 t CB Close
5548
LR2 after 81-1
222
Function
Setting Options
81 O/U Freq.
OFF
ON f>
ON f<
Load Restore
1 .. 3600 sec
Load Restore
1 .. 10
Load Restore
ON
Load Restore
OFF
Load Restore
40.00 .. 60.00 Hz
Load Restore
50.00 .. 70.00 Hz
Load Restore
0.02 .. 2.00 Hz
Load Restore
0 .. 10800 sec
Load Restore
0.00 .. 2.00 Hz
Load Restore
0 .. 10800 sec
Load Restore
0.01 .. 32.00 sec
Load Restore
YES
NO
Load Restore
YES
NO
Load Restore
YES
NO
Load Restore
YES
NO
Load Restore
ON
Load Restore
OFF
Load Restore
40.00 .. 60.00 Hz
Load Restore
50.00 .. 70.00 Hz
Load Restore
0.02 .. 2.00 Hz
Load Restore
0 .. 10800 sec
Load Restore
0.00 .. 2.00 Hz
Load Restore
0 .. 10800 sec
Load Restore
0.01 .. 32.00 sec
Load Restore
YES
NO
Default Setting
Comments
OFF
81-4 Over/Under Frequency
Protection
3600 sec
Load restoration monitor
time
2
Load restoration maximal
no. of cycles
OFF
Load restoration element 1
49.50 Hz
Load restoration elem. 1
start frequency
59.50 Hz
Load restoration elem. 1
start frequency
0.04 Hz
Load restoration element 1
Pickup
600 sec
Load restoration element 1
Pickup time
0.02 Hz
Load restoration element 1
Dropout
60 sec
Load restoration element 1
Dropout time
1.00 sec
Load restoration element 1
CB Close time
NO
Load restoration element 1
after 81-1
NO
Load restoration element 1
after 81-2
NO
Load restoration element 1
after 81-3
NO
Load restoration element 1
after 81-4
OFF
Load restoration element 2
49.00 Hz
Load restoration elem. 2
start frequency
59.00 Hz
Load restoration elem. 2
start frequency
0.04 Hz
Load restoration element 2
Pickup
600 sec
Load restoration element 2
Pickup time
0.02 Hz
Load restoration element 2
Dropout
60 sec
Load restoration element 2
Dropout time
1.00 sec
Load restoration element 2
CB Close time
NO
Load restoration element 2
after 81-1
SIPROTEC 4, 7RW80, Manual
C53000-G1140-C233-4, Edition 07.2018