With single-phase voltage transformers, a direct comparison of the measured quantities with the threshold
values is carried out and the parameterization of the characteristic quantity switchover is ignored.
NOTE
i
i
If parameter 213 VT Connect. 3ph is set to Vph-g, VSyn, the voltage measured by voltage trans-
former 1 is always used for voltage protection. Then parameters 614 and 615 are not available.
NOTE
i
i
If parameter 213 VT Connect. 3ph is set to Vab, Vbc, VSyn or Vab, Vbc or Vab, Vbc, Vx, the
setting option Vph-n for parameter 614 and 615 is not available.
2.1.3.3

Settings

Addresses which have an appended "A" can only be changed with DIGSI, under "Additional Settings".
Addr.
Parameter
202
Vnom PRIMARY
203
Vnom SECONDARY
206A
Vph / Vdelta
209
PHASE SEQ.
210A
TMin TRIP CMD
211A
TMax CLOSE CMD
213
VT Connect. 3ph
214
Rated Frequency
220
Threshold BI 1
221
Threshold BI 2
222
Threshold BI 3
223
Threshold BI 4
224
Threshold BI 5
SIPROTEC 4, 7RW80, Manual
C53000-G1140-C233-4, Edition 07.2018
Setting Options
0.10 .. 800.00 kV
34 .. 225 V
1.00 .. 3.00
A B C
A C B
0.01 .. 32.00 sec
0.01 .. 32.00 sec
Van, Vbn, Vcn
Vab, Vbc, VGnd
Vab, Vbc, VSyn
Vab, Vbc
Vph-g, VSyn
Vab, Vbc, Vx
50 Hz
60 Hz
Thresh. BI 176V
Thresh. BI 88V
Thresh. BI 19V
Thresh. BI 176V
Thresh. BI 88V
Thresh. BI 19V
Thresh. BI 176V
Thresh. BI 88V
Thresh. BI 19V
Thresh. BI 176V
Thresh. BI 88V
Thresh. BI 19V
Thresh. BI 176V
Thresh. BI 88V
Thresh. BI 19V
Default Setting
Comments
20.00 kV
Rated Primary Voltage
100 V
Rated Secondary Voltage (L-L)
1.73
Matching ratio Phase-VT To Open-
Delta-VT
A B C
Phase Sequence
0.15 sec
Minimum TRIP Command Duration
1.00 sec
Maximum Close Command Dura-
tion
Van, Vbn, Vcn
VT Connection, three-phase
50 Hz
Rated Frequency
Thresh. BI 176V
Threshold for Binary Input 1
Thresh. BI 176V
Threshold for Binary Input 2
Thresh. BI 176V
Threshold for Binary Input 3
Thresh. BI 176V
Threshold for Binary Input 4
Thresh. BI 176V
Threshold for Binary Input 5
Functions