Siemens SIPROTEC 4 Manual page 21

Voltage and frequency protection
Hide thumbs Also See for SIPROTEC 4:
Table of Contents

Advertisement

Monitoring Functions
Increased reliability due to monitoring of the internal measurement circuits as well as the hardware and
software
Monitoring of the current transformer and voltage transformer secondary circuits using sum and
symmetry supervision with optional protection function blocking
Broken-wire Monitoring of Voltage Transformer Circuits
Trip circuit monitoring possible
Phase rotation check.
Flexible Protective Functions
Up to 20 customizable protection functions with three-phase or single-phase operation
Any calculated or directly measured quantity can be evaluated on principle
Standard protection logic with definite time characteristic
Internal and configurable pickup and dropout delay
Modifiable message texts.
Synchrocheck
Check of the synchronism conditions or de-energized state before manual closing of the circuit breaker
Fast measurement of the voltage difference ΔV, the phase angle difference Δϕ and the frequency differ-
ence Δf
Setable minimum and maximum voltage
Measurement also possible via transformer without external intermediate matching transformer
Measuring voltages optionally phase–to–phase or phase–to–ground.
Overecxitation Protection
Calculation of the V/f ratio V/f
Adjustable warning and tripping stage
Standard characteristic or arbitrary trip characteristic selectable for calculation of the thermal stress.
Jump of Voltage Vector
Sensitive phase jump detection to be used for network disconnection.
Phase Rotation
Selectable ABC or ACB by setting (static) or binary input (dynamic).
User Defined Functions
Freely programmable linking of internal and external signals in order to implement user-defined logic
functions
All standard logic functions (AND, OR, NOT, EXCLUSIVE-OR, etc.)
Time delays and limit value interrogations
Processing of measured values, including zero suppression, adding a knee curve for a transducer input,
and live-zero monitoring.
Linking of multiple devices for load restoration with prioritization of the stages
SIPROTEC 4, 7RW80, Manual
C53000-G1140-C233-4, Edition 07.2018
Introduction
1.3 Characteristics
21

Advertisement

Table of Contents
loading

This manual is also suitable for:

Siprotec 7rw80

Table of Contents