Siemens SIPROTEC 4 Manual page 221

Voltage and frequency protection
Hide thumbs Also See for SIPROTEC 4:
Table of Contents

Advertisement

Addr.
Parameter
5113A 27-1 DOUT RATIO
5114A 27-2 DOUT RATIO
5130
27 Vp<
5131
27 Vp<
5132
27 T Vp<
5133
Pickup - Time
5201
VT BROKEN WIRE
5202
Σ V>
5203
Vph-ph max<
5204
Vph-ph min<
5205
Vph-ph max-min>
5208
T DELAY ALARM
5401
FCT 81 O/U
5402
Vmin
5402
Vmin
5403
81-1 PICKUP
5404
81-1 PICKUP
5405
81-1 DELAY
5406
81-2 PICKUP
5407
81-2 PICKUP
5408
81-2 DELAY
5409
81-3 PICKUP
5410
81-3 PICKUP
5411
81-3 DELAY
5412
81-4 PICKUP
5413
81-4 PICKUP
5414
81-4 DELAY
5415A DO differential
5421
FCT 81-1 O/U
5422
FCT 81-2 O/U
5423
FCT 81-3 O/U
SIPROTEC 4, 7RW80, Manual
C53000-G1140-C233-4, Edition 07.2018
Function
Setting Options
27/59 O/U Volt.
1.01 .. 3.00
27/59 O/U Volt.
1.01 .. 3.00
27/59 O/U Volt.
10 .. 210 V
27/59 O/U Volt.
10 .. 120 V
27/59 O/U Volt.
0.1 .. 5.0 sec
27/59 O/U Volt.
0.05 .. 1.00
0.01 .. 999.00
Meas-
ON
urem.Superv
OFF
Meas-
1.0 .. 100.0 V
urem.Superv
Meas-
1.0 .. 100.0 V
urem.Superv
Meas-
1.0 .. 100.0 V
urem.Superv
Meas-
10.0 .. 200.0 V
urem.Superv
Meas-
0.00 .. 32.00 sec
urem.Superv
81 O/U Freq.
OFF
ON
81 O/U Freq.
10 .. 150 V
81 O/U Freq.
20 .. 150 V
81 O/U Freq.
40.00 .. 60.00 Hz
81 O/U Freq.
50.00 .. 70.00 Hz
81 O/U Freq.
0.00 .. 100.00 sec
81 O/U Freq.
40.00 .. 60.00 Hz
81 O/U Freq.
50.00 .. 70.00 Hz
81 O/U Freq.
0.00 .. 100.00 sec
81 O/U Freq.
40.00 .. 60.00 Hz
81 O/U Freq.
50.00 .. 70.00 Hz
81 O/U Freq.
0.00 .. 100.00 sec
81 O/U Freq.
40.00 .. 60.00 Hz
81 O/U Freq.
50.00 .. 70.00 Hz
81 O/U Freq.
0.00 .. 100.00 sec
81 O/U Freq.
0.02 .. 1.00 Hz
81 O/U Freq.
OFF
ON f>
ON f<
81 O/U Freq.
OFF
ON f>
ON f<
81 O/U Freq.
OFF
ON f>
ON f<
Functions, Settings, Information
Default Setting
Comments
1.20
27-1 Dropout Ratio
1.20
27-2 Dropout Ratio
75 V
27 Pickup Vp<
45 V
27 Pickup Vp<
1.0 sec
27 T Vp< Time Delay
Pickup - Time
OFF
VT broken wire supervision
8.0 V
Threshold voltage sum
16.0 V
Maximum phase to phase
voltage
16.0 V
Minimum phase to phase
voltage
16.0 V
Symmetry phase to phase
voltages
1.25 sec
Alarm delay time
OFF
81 Over/Under Frequency
Protection
65 V
Minimum required voltage
for operation
35 V
Minimum required voltage
for operation
49.50 Hz
81-1 Pickup
59.50 Hz
81-1 Pickup
60.00 sec
81-1 Time Delay
49.00 Hz
81-2 Pickup
59.00 Hz
81-2 Pickup
30.00 sec
81-2 Time Delay
47.50 Hz
81-3 Pickup
57.50 Hz
81-3 Pickup
3.00 sec
81-3 Time delay
51.00 Hz
81-4 Pickup
61.00 Hz
81-4 Pickup
30.00 sec
81-4 Time delay
0.02 Hz
Dropout differential
OFF
81-1 Over/Under Frequency
Protection
OFF
81-2 Over/Under Frequency
Protection
OFF
81-3 Over/Under Frequency
Protection
E.2 Settings