Voltage and frequency protection
Hide thumbs Also See for SIPROTEC 4:
Table of Contents

Advertisement

Addr.
Parameter
302
CHANGE
401
WAVEFORM-
TRIGGER
402
WAVEFORM DATA
403
MAX. LENGTH
404
PRE. TRIG. TIME
405
POST REC. TIME
406
BinIn CAPT.TIME
610
FltDisp.LED/LCD
611
Spont. FltDisp.
614A
OP. QUANTITY 59
615A
OP. QUANTITY 27
640
Start image DD
1101
FullScaleVolt.
4301
FCT 24 V/f
4302
24-1 PICKUP
4303
24-1 DELAY
4304
24-2 PICKUP
4305
24-2 DELAY
4306
24-t(V/f=1.05)
4307
24-t(V/f=1.10)
4308
24-t(V/f=1.15)
4309
24-t(V/f=1.20)
4310
24-t(V/f=1.25)
4311
24-t(V/f=1.30)
4312
24-t(V/f=1.35)
SIPROTEC 4, 7RW80, Manual
C53000-G1140-C233-4, Edition 07.2018
Function
Setting Options
Change Group
Group A
Group B
Group C
Group D
Binary Input
Protocol
Osc. Fault Rec.
Save w. Pickup
Save w. TRIP
Start w. TRIP
Osc. Fault Rec.
Fault event
Pow.Sys.Flt.
Osc. Fault Rec.
0.30 .. 5.00 sec
Osc. Fault Rec.
0.05 .. 0.50 sec
Osc. Fault Rec.
0.05 .. 0.50 sec
Osc. Fault Rec.
0.10 .. 5.00 sec
Device, General Target on PU
Target on TRIP
Device, General YES
NO
P.System Data 1 Vphph
Vph-n
V1
V2
P.System Data 1 V1
Vphph
Vph-n
Device, General image 1
image 2
image 3
P.System Data 2 0.10 .. 800.00 kV
24 V/f Overflux
OFF
ON
24 V/f Overflux
1.00 .. 1.20
24 V/f Overflux
0.00 .. 60.00 sec
24 V/f Overflux
1.00 .. 1.40
24 V/f Overflux
0.00 .. 60.00 sec
24 V/f Overflux
0 .. 20000 sec
24 V/f Overflux
0 .. 20000 sec
24 V/f Overflux
0 .. 20000 sec
24 V/f Overflux
0 .. 20000 sec
24 V/f Overflux
0 .. 20000 sec
24 V/f Overflux
0 .. 20000 sec
24 V/f Overflux
0 .. 20000 sec
Functions, Settings, Information
Default Setting
Comments
Group A
Change to Another Setting
Group
Save w. Pickup
Waveform Capture
Fault event
Scope of Waveform Data
2.00 sec
Max. length of a Waveform
Capture Record
0.10 sec
Captured Waveform Prior to
Trigger
0.10 sec
Captured Waveform after
Event
0.50 sec
Capture Time via Binary
Input
Target on PU
Fault Display on LED / LCD
NO
Spontaneous display of
flt.annunciations
Vphph
Opera. Quantity for 59
Overvolt. Prot.
V1
Opera. Quantity for 27
Undervolt. Prot.
image 1
Start image Default Display
20.00 kV
Measurem:FullScale-
Voltage(Equipm.rating)
OFF
24 Overexcit. Protection
(Volt/Hertz)
1.10
24-1 V/f Pickup
10.00 sec
24-1 V/f Time Delay
1.40
24-2 V/f Pickup
1.00 sec
24-2 V/f Time Delay
20000 sec
24 V/f = 1.05 Time Delay
6000 sec
24 V/f = 1.10 Time Delay
240 sec
24 V/f = 1.15 Time Delay
60 sec
24 V/f = 1.20 Time Delay
30 sec
24 V/f = 1.25 Time Delay
19 sec
24 V/f = 1.30 Time Delay
13 sec
24 V/f = 1.35 Time Delay
E.2 Settings
219