Siemens SIPROTEC 4 Manual page 163

Voltage and frequency protection
Hide thumbs Also See for SIPROTEC 4:
Table of Contents

Advertisement

Profibus FO (DP)
FO connector type
Terminal
Transmission speed
Recommended:
Optical wavelength
Laser Class 1 according to EN 60825-1/-2
Permissible optical signal attenuation
Bridgeable distance
DNP3.0 /MODBUS RS485
Terminal
Test voltage (PELV)
Transmission speed
Bridgeable distance
DNP3.0 /MODBUS FO
FO connector type
Terminal
Transmission speed
Optical wavelength
Laser Class 1 according to EN 60825-1/-2
Permissible optical signal attenuation
Bridgeable distance
Ethernet electrical (EN 100) for DIGSI and IEC61850
Terminal
Test voltage (with regard to the socket)
(PELV)
Transmission speed
Bridgeable distance
Ethernet optical (EN 100) for DIGSI and IEC61850
Terminal
Transmission speed
Optical wavelength
Bridgeable distance
SIPROTEC 4, 7RW80, Manual
C53000-G1140-C233-4, Edition 07.2018
ST connector
Double ring
Back case bottom, mounting location "B"
up to 1.5 MBd
> 500 kBd with normal casing
λ = 820 nm
When using glass fiber 50/125 μm or glass fiber 62.5/125 μm
max. 8 dB, with glass fiber 62.5/125 μm
max. 1.5 km
Back case bottom, mounting location "B", 9- pin DSUB socket
500 V; 50 Hz
up to 19,200 Bd
max. 1 km
ST connector transmitter/receiver
Back case bottom, mounting location "B"
up to 19,200 Bd
λ = 820 nm
When using glass fiber 50 μm/125 μm or glass fiber 62.5/125 μm
max. 8 dB, with glass fiber 62.5/125 μm
max. 1.5 km
Back case bottom, mounting location "B",
2 x RJ45 socket
100BaseT according to IEEE802.3
500 V; 50 Hz
100 MBit/s
20 m
Back case bottom, mounting location "B",
Duplex-LC, 100BaseF according to IEEE802.3
100 MBit/s
1300 nm
max. 2 km (1.24 mi)
Technical Data
4.1 General Device Data
163