Time Delays
The time delay T DELTA PHI (address 4603) should be left at zero, unless you wish to transmit the trip indi-
cation with a delay to a logic (CFC), or to leave enough time for an external blocking to take effect.
After expiry of the timer T RESET (address 4604), the protection function is automatically reset. The reset
time depends on the decoupling policy. It must have expired before the circuit breaker is reclosed. Where the
automatic reset function is not used, the timer is set to ∞. The reset signal must come in this case from the
binary input (circuit breaker auxiliary contact).
The timer T BLOCK with reset delay (address 4607) helps to avoid overfunctioning when voltages are
connected or disconnected. Normally the default setting need not be changed. Any change can be performed
with the DIGSI communication software (advanced parameters). It must be kept in mind that T BLOCK should
not be set less than the measuring window for vector jump measurement (150 ms).

Settings

2.9.3
Addresses which have an appended "A" can only be changed with DIGSI, under "Additional Settings".
Addr.
Parameter
4601
VECTOR JUMP
4602
DELTA PHI
4603
T DELTA PHI
4604
T RESET
4605A
V MIN
4606A
V MAX
4607A
T BLOCK

Information List

2.9.4
No.
Information
5581
>VEC JUMP block
5582
VEC JUMP OFF
5583
VEC JMP BLOCKED
5584
VEC JUMP ACTIVE
5585
VEC JUMP Range
5586
VEC JUMP pickup
5587
VEC JUMP TRIP
SIPROTEC 4, 7RW80, Manual
C53000-G1140-C233-4, Edition 07.2018
Setting Options
OFF
ON
2 .. 30 °
0.00 .. 60.00 sec
0.10 .. 60.00 sec
10.0 .. 125.0 V
10.0 .. 170.0 V
0.00 .. 60.00 sec
Type of
Comments
Informa-
tion
SP
>BLOCK Vector Jump
OUT
Vector Jump is switched OFF
OUT
Vector Jump is BLOCKED
OUT
Vector Jump is ACTIVE
OUT
Vector Jump not in measurement range
OUT
Vector Jump picked up
OUT
Vector Jump TRIP
Default Setting
Comments
OFF
Jump of Voltage Vector
10 °
Jump of Phasor DELTA PHI
0.00 sec
T DELTA PHI Time Delay
5.00 sec
Reset Time after Trip
80.0 V
Minimal Operation Voltage V MIN
130.0 V
Maximal Operation Voltage V MAX
0.15 sec
Time Delay of Blocking
Functions
2.9 Jump of Voltage Vector