Addr.
Parameter
6107
SYNC V1<V2>
6108
SYNC V1>V2<
6109
SYNC V1<V2<
6110A
Direct CO
6111A
TSUP VOLTAGE
6112
SYN. DURATION
6113A
25 Synchron
6121
Balancing V1/V2
6122A
ANGLE ADJUSTM.
6123
CONNECTIONof V2
6125
VT Vn2, primary
6150
dV SYNCHK V2>V1
6151
dV SYNCHK V2<V1
6152
df SYNCHK f2>f1
6153
df SYNCHK f2<f1
6154
dα SYNCHK α2>α1
6155
dα SYNCHK α2<α1

Information List

2.7.8
No.
Information
170.0001 >25-1 act
170.0043 >25 Sync requ.
170.0049 25 CloseRelease
170.0050 25 Sync. Error
170.0051 25-1 BLOCK
170.2007 25 Measu. req.
170.2008 >BLK 25-1
170.2009 >25direct CO
170.2011 >25 Start
170.2012 >25 Stop
170.2013 >25 V1>V2<
SIPROTEC 4, 7RW80, Manual
C53000-G1140-C233-4, Edition 07.2018
Setting Options
YES
NO
YES
NO
YES
NO
YES
NO
0.00 .. 60.00 sec
0.01 .. 1200.00 sec
YES
NO
0.50 .. 2.00
0 .. 360 °
A-B
B-C
C-A
0.10 .. 800.00 kV
0.5 .. 50.0 V
0.5 .. 50.0 V
0.01 .. 2.00 Hz
0.01 .. 2.00 Hz
2 .. 80 °
2 .. 80 °
Type of
Comments
Informa-
tion
SP
>25-group 1 activate
SP
>25 Synchronization request
OUT
25 Sync. Release of CLOSE Command
OUT
25 Synchronization Error
OUT
25-group 1 is BLOCKED
SP
25 Sync. Measuring request of Control
SP
>BLOCK 25-group 1
SP
>25 Direct Command output
SP
>25 Start of synchronization
SP
>25 Stop of synchronization
SP
>25 Switch to V1> and V2<
Default Setting
Comments
NO
ON-Command at V1< and V2>
NO
ON-Command at V1> and V2<
NO
ON-Command at V1< and V2<
NO
Direct ON-Command
0.10 sec
Supervision time of V1>;V2> or
V1<;V2<
30.00 sec
Maximum duration of
synchronism-check
YES
Switching at synchronous condi-
tion
1.00
Balancing factor V1/V2
0 °
Angle adjustment (transformer)
A-B
Connection of V2
20.00 kV
VT nominal voltage V2, primary
5.0 V
Maximum voltage difference
V2>V1
5.0 V
Maximum voltage difference
V2<V1
0.10 Hz
Maximum frequency difference
f2>f1
0.10 Hz
Maximum frequency difference
f2<f1
10 °
Maximum angle difference
alpha2>alpha1
10 °
Maximum angle difference
alpha2<alpha1