NAiS FP Series User Manual page 54

Applicable plc
Hide thumbs Also See for FP Series:
Table of Contents

Advertisement

FPΣ
Installation space
Leave at least 50 mm/1.97 in. of space between the wiring ducts of the unit and other
devices to allow heat radiation and unit replacement.
50 mm/1.97 in.
or more
50 mm/1.97 in.
or more
Figure 25: FPΣ Installation space - 1
Maintain a minimum of 100 mm/3.937 in. between devices to avoid adverse affects from
noise and heat when installing a device or panel door to the front of the PLC unit.
100 mm/
3.937 in.
or more
Figure 26: FPΣ Installation space - 2
Keep the first 100 mm/3.937 in. from the front surface of the control unit open in order
to allow room for programming tool connections and wiring.
Panel door
5.1 Installation
5 - 5